Littelfuse 201-100-DPDT, 201-DPDT Series, 3-Phase Voltage/Phase Monitor, Voltage Sensing AC 95 ~ 120VAC, DPDT (2 Form C)
Pickup available at 220 Alden Road
Usually ready in 24 hours
Use this text to encourage communication or promote sharing on social networks.
The 201-100/200-DPDT series is an 11-pin octal base, plug-in voltage monitor designed to protect three-phase motors regardless of size. The 201-100-DPDT is used on 95–120 V ac, 50/60 Hz motors to prevent damage caused by low voltage. The 201-200-DPDT is used on 190–240 V ac, 50/60 Hz motors to prevent damage caused by incoming voltage problems. These monitors feature two isolated sets of contacts that are ideal for use with two control circuits with different voltages. The unique microcontroller-based voltage and voltage-sensing circuit constantly monitors the voltage to detect harmful power line conditions. When a harmful condition is detected, the MotorSaver deactivates its output relay after a specified trip delay. The output relays reactivate after power line conditions return to an acceptable level and a specified amount of time has elapsed (restart delay). The trip delay prevents nuisance tripping due to rapidly fluctuating power line conditions.
Notes:
Must use Model OT11PC socket for UL Rating.
Manufacturer’s recommended screw terminal torque for the RB series and OT series octal sockets is 12 in.-lbs.
Pre-order 6-8 Weeks
Frequency | 50/60Hz |
Input Characteristics | |
Line Voltage | 201-100-DPDT 95–120 V ac 201-200-DPDT 190–240 V ac |
Functional Characteristics | |
Low Voltage (% of setpoint) |
Trip 90%±1% Reset 93%±1% |
Voltage Unbalance |
Trip 6% Reset 4.5% |
Trip Delay Time |
Low Voltage 4 seconds Unbalance, Phasing Faults 2 seconds |
Restart Delay Time | After a Fault or Complete Power Loss 2 seconds |
Output Characteristics | |
Output Contact Rating (DPDT) |
Pilot Duty 480 VA @ 240 V ac General Purpose 10 A @ 240 V ac |
General Characteristics | |
Temperature Range | -40° to 70 °C (-40° to 158 °F) |
Maximum Input Power | 5 W |
Standards Passed |
Electrostatic Discharge (ESD) IEC 61000-4-2, Level 3, 6 kV contact, 8 kV air Radio Frequency |
Dimensions |
H 44.5 mm (1.75”) W 60.3 mm (2.38'') D 104.8 mm (4.13”) |
Weight | 0.65 lb. (10.4 oz., 294.84 g) |
Mounting Method | DIN rail or surface mount (plug in to OT11PC socket) |
Socket Available | Model OT11PC (UL Rated 300 V) |
Certification & Compliance |
UL UL508 (File #E68520) |