Littelfuse 201-100-SP-DPDT, 201-SP-DPDT Series, Single-phase voltage/phase monitor, Voltage Sensing AC 95 ~ 120VAC, DPDT (2 Form C)

In stock
SKU: 201-100-SP-DPDT
Regular price $289.11
Rated voltage
Phase
Description

Use this text to encourage communication or promote sharing on social networks.

You can also add links

The 201-SP-DPDT series is an 8-pin octal base, plug-in voltage monitor designed to protect single-phase motors regardless of their size. The 201-100-SP-DPDT is used on 95–120 V ac, 50/60 Hz motors to prevent damage caused by low voltage. The 201-200-SP-DPDT is used on 190–240 V ac, 50/60 Hz motors. These monitors feature two isolated sets of contacts that are ideal for use with two control circuits with different voltages. The unique microcontroller-based voltage and voltage-sensing circuit constantly monitors the voltage to detect harmful power line conditions. When a harmful condition is detected, the MotorSaver’s output relays are deactivated after a specified trip delay. The output relays reactivate after power line conditions return to an acceptable level and a specified amount of time has elapsed (restart delay). The trip delay prevents nuisance tripping due to rapidly fluctuating power line conditions.

Input Characteristics  
Line Voltage 201-100-SP-DPDT:    95-120VAC
201-200-SP-DPDT:    190-240VAC
Frequency 50/60 Hz
Functional Characteristics
Low Voltage (% of setpoint) Trip        90% +/-1%
Reset     93% +/-1%
Trip Delay Time Low Voltage:    4 seconds
Restart Delay Time After a Complete Power Loss:    2 seconds
Output Characteristics
Output Contact Rating (DPDT) Pilot Duty:               480 VA @ 240 V ac
General Purpose:    10 A @ 240 V ac
General Characteristics
Ambient Temperature Range Operating:    -40° to 70°C (-40° to 158°F)
Storage:        -40° to 80°C (-40° to 176°F)
Maximum Input Power 5 W
Relative Humidity 10-95%, non-condensing per IEC 68-2-3
Standards Passed
Electrostatic Discharge (ESD) IEC 61000-4-2, Level 3, 6kV contact, 8kV air
Radio Frequency Immunity, Radiated 150MHz, 10V/m
Fast Transient Burst IEC 61000-4-4, Level 3, 3.5kV input power and controls
Safety Marks UL (OT08PC octal socket required):  UL508 (File #E68520)
CE:  IEC 60947-6-2
Dimensions H 44.45 mm (1.75”)
W 60.325 mm (2.375”)
D 104.775 mm (4.125”) (with socket)
Weight 0.65 lb. (10.4 oz., 294.84 g)
Mounting Method DIN rail or surface mount (plug in to OT08PC socket)
Socket Available Model OT08PC (UL Rating 600 V)