Littelfuse 201575-AU, 201A-AU Series, 3-Phase Voltage/Phase Monitor, Voltage Asymmetry, Voltage Sensing AC 475 ~ 600VAC, DIN-rail or surface mountable

In stock
SKU: 201575-AU
Regular price $284.02
Rated voltage
Phase
 More payment options

Pickup available at 220 Alden Road

Usually ready in 24 hours

Use this text to encourage communication or promote sharing on social networks.

You can also add links

The 201A-AU series is a three-phase, auto-ranging, dual-range voltage monitor that protects 190–480 V ac, 50/60 Hz motors regardless of their size. This monitor provides a user-selectable nominal voltage setpoint and will automatically select between the 200 V and 400 V range. Additional adjustment knobs allow the user to set a 1–30 second trip delay, a manual restart or 1–500 second restart delay, and a 2–8% voltage unbalance trip point. It includes advanced, single LED diagnostics where color and light patterns distinguish between faults and normal conditions. This unique microcontrollerbased voltage and phase-sensing unit constantly monitors the three-phase voltages to detect harmful power line conditions. When a harmful condition is detected, the output relay is deactivated after a specified trip delay. The output relay reactivates after power line conditions return to acceptable levels for a specified restart delay time (or manual reset).

Frequency 50/60Hz
Functional Characteristics
Low Voltage (% of setpoint) Trip                 90%±1%
Reset               93%±1%
High Voltage (% of setpoint) Trip                 110% ±1%
Reset               107% ±1%
Voltage Unbalance (NEMA) Trip         2–8% adjustable
Reset      Trip setting minus 1% (5–8%)
                Trip setting minus 0.5% (2–4%)
Trip Delay Time High, Low and Unbalanced Voltage:  1–30 seconds adjustable
Single-Phasing Faults 1 second fixed
Restart Delay Time After a Fault:   Manual, 1–500 seconds adjustable
After a Complete Power Loss:    Manual, 1–500 seconds adjustable
Output Contact Rating (1-Form C)

Pilot Duty                  480 VA @ 240 V ac
General Purpose       10 A @ 240 V ac
General Characteristics
Ambient Temperature Range Operating    -40° to 70 °C (-40° to 158 °F)
Storage        -40° to 80 °C (-40° to 176 °F)
Trip & Reset Accuracy ±1%
Maximum Input Power 5 W
Relative Humidity 10–95%, non-condensing per IEC 68-2-3
Terminal Torque 12 in.-lbs. (for OT08-PC socket)
Wire Size 12–22 AWG solid or stranded
Transient Protection (Internal) 2500 V for 10 ms
Standards Passed

Electrostatic Discharge (ESD)  IEC 61000-4-2, Level 3, 6 kV contact, 8 kV air
Radio Frequency Immunity Radiated    150MHz, 10 V/m
Fast Transient Burst   IEC 61000-4-4, Level 3, 3.5 kV input power & controls

Dimensions H 44.5 mm (1.75”)
W 60.3 mm (2.38'')
D 104.8 mm (4.13”)
Enclosure Polycarbonate
Weight 0.7 lb. (11.2 oz., 317.51 g)
Mounting Method DIN-rail or surface mount (plug in to OT08PC socket)
Socket Available OT08PC (UL Rating 600 V)
Certification & Compliance UL        UL508 (File #E68520)