Littelfuse 202, 202 Series, 3-Phase Voltage Monitor, Voltage Asymmetry, Voltage Sensing AC 190 ~ 480VAC, SPDT (1 Form C)

In stock
SKU: 202
Regular price $188.17
Rated voltage
Phase
Description

Use this text to encourage communication or promote sharing on social networks.

You can also add links

The 202 series is a 3-phase, auto-ranging, dual-range voltage monitor that protects 190–480 V ac, 50*/60 Hz motors regardless of size. The 202-RP (and the 202-575-RP for 475–600 V ac) monitors the phase rotation of 3-phase systems and trips on reverse-phase only. Critical applications include fan motors, scroll compressors, grinders, conveyor systems, elevators and escalators. Both products provide a user selectable nominal voltage setpoint and automatically select between the 200 V and 400 V range.

This unique microcontroller-based voltage and phase-sensing device constantly monitors the 3-phase voltages to detect harmful power line conditions. When a harmful condition is detected, the MotorSaver’s output relay is deactivated after a specified trip delay. The output relay reactivates after power line conditions return to acceptable levels for a specified amount of restart delay time (or a manual reset). The 202 series includes advanced single LED diagnostics. Five different light patterns distinguish between faults and normal conditions. The status light turns green and the relay is activated when rotation is correct.

*Note: 50 Hz will increase all delay timers by 20 %. CE Pending

Frequency 50*/60Hz
Functional Characteristics
Phase Sequence ABC
Low Voltage (% of setpoint) Trip                 90%
Reset               93%
High Voltage (% of setpoint) Trip                 110% 
Reset               107% 
Voltage Unbalance (NEMA) Trip                  6 %
Reset               4.5 % 
Trip Delay Time High and Low Voltage :         4 seconds
Unbalance & Phasing Faults :2 seconds
Restart Delay Time After a Fault:  Manual, 2–300 seconds adj.
After a Complete Power Loss: Manual, 2–300 seconds adj.
Output Characteristics
Output Contact Rating (SPDT) Pilot Duty:            480 VA @ 240 V ac
General Purpose: 10 A @ 240 V ac
General Characteristics
Temperature Range -40° to 70°C (-40° to 158°F)
Trip & Reset Accuracy ±1%
Repeatability ±0.5 %
Maximum Input Power 5 W
Relative Humidity 95 %, non-condensing
Transient Protection IEC 61000-4-5, ±4 kV
Hi-potential Test Meets UL 508 (2x rated V+1000 V for 1 minute)
Termination 0.25” male quick connect
Safety Marks
UL Recognized UL 508 (File #E68520)
Dimensions H 63.5 mm (2.5”)
W 63.5 mm (2.5'')
D 35.56 mm (1.4”)
Weight 0.5 lb. (8 oz., 226.8 g)
Mounting Method 1/4” socket head cap screw (customer supplied)