Littelfuse 232-INSIDER, 232-Insider Series, Single-Phase Pump Monitor, Voltage Sensing AC 230VAC, 1 Phase
FOR ALL ORDERS OUTSIDE CANADA, CUSTOMERS ARE RESPONSIBLE FOR ANY IMPORT DUTIES, TARIFFS, TAXES, AND CUSTOMS FEES THAT MAY APPLY TO THEIR ORDERS.
Couldn't load pickup availability
Use this text to encourage communication or promote sharing on social networks.
The single-phase 232-Insider PumpSaver® fits inside ⅓, ½, ¾, and 1 hp, 230 V Grundfos control boxes. The PumpSaver 232-Insider is designed to protect single-phase pumps from dry-well, dead-head, jammed impellers, overvoltage, and undervoltage conditions. Typical applications include residential water wells, commercial water wells, irrigation wells, and golf course systems.
A calibration adjustment allows the 232-Insider to be calibrated to your specific pumping application, reducing the possibility of false or nuisance tripping. A unique microcontroller-based voltage and current-sensing circuit constantly monitors the incoming power for fluctuations, overcurrent, and undercurrent. When an abnormality, such as loss of suction is detected, the 232-Insider deactivates its output relay and directly disconnects the pump motor. The 232-Insider then begins its user-selectable restart delay (dry-well recovery) timer. When the timer counts to zero or power is removed and reapplied, the 232-Insider reactivates its output relay and turns the pump back on. By leaving the restart delay knob in the reset position, the 232-Insider will operate in manual reset mode. An infrared LED communicates directly with a hand-held diagnostic tool called the Informer*.
Note: The use of flow restrictors or unusually high head pressures at the time of calibration may interfere with the detection of dead-head conditions.
*Note: 50 Hz will increase all delay timers by 20 %
Pre-order 6-8 Weeks
| Functional Characteristics | |
| 1 Phase Line Voltage (±10 %) | 230 V ac |
| Load Range | 1 ⁄3–1 hp |
| Frequency | 50*/60 Hz |
| Operating Points | |
| Overload | 125 % of Cal. Point |
| Underload (dry well) | 80 % or 87 % of calibrated run power |
| High Voltage Reset Point | 265 |
| Low Voltage Reset Point | 190 |
| Trip Delay Time (Overload) | 5 sec. |
| Trip Delay Time (Dry well) | 4 sec. |
| Restart Delay Time | |
| Overvoltage/Undervoltage Delay | 2 sec |
| All other faults (dry-well rec. timer) | Manual, 2–225 min. |
| Output Contact Rating (SPST) | 1 hp @ 240 V ac (17 amps max.) |
| Weight | 10 oz. |
| Power Consumption | 5 Watts (max.) |
| Certification & Compliance | cULus |

