The single-phase 232-Insider PumpSaver® fits inside ⅓, ½, ¾, and 1 hp, 230 V Grundfos control boxes. The PumpSaver 232-Insider is designed to protect single-phase pumps from dry-well, dead-head, jammed impellers, overvoltage, and undervoltage conditions. Typical applications include residential water wells, commercial water wells, irrigation wells, and golf course systems.

A calibration adjustment allows the 232-Insider to be calibrated to your specific pumping application, reducing the possibility of false or nuisance tripping. A unique microcontroller-based voltage and current-sensing circuit constantly monitors the incoming power for fluctuations, overcurrent, and undercurrent. When an abnormality, such as loss of suction is detected, the 232-Insider deactivates its output relay and directly disconnects the pump motor. The 232-Insider then begins its user-selectable restart delay (dry-well recovery) timer. When the timer counts to zero or power is removed and reapplied, the 232-Insider reactivates its output relay and turns the pump back on. By leaving the restart delay knob in the reset position, the 232-Insider will operate in manual reset mode. An infrared LED communicates directly with a hand-held diagnostic tool called the Informer*.

Note: The use of flow restrictors or unusually high head pressures at the time of calibration may interfere with the detection of dead-head conditions.

*Note: 50 Hz will increase all delay timers by 20 %

Pre-order 6-8 Weeks

Functional Characteristics  
1 Phase Line Voltage (±10 %) 230 V ac
Load Range 1 ⁄3–1 hp
Frequency 50*/60 Hz
Operating Points
Overload 125 % of Cal. Point
Underload (dry well) 80 % or 87 % of calibrated run power
High Voltage Reset Point 265
Low Voltage Reset Point 190
Trip Delay Time (Overload) 5 sec.
Trip Delay Time (Dry well) 4 sec.
Restart Delay Time
Overvoltage/Undervoltage Delay 2 sec
All other faults (dry-well rec. timer) Manual, 2–225 min.
Output Contact Rating (SPST) 1 hp @ 240 V ac (17 amps max.)
Weight 10 oz.
Power Consumption 5 Watts (max.)
Certification & Compliance cULus