Littelfuse 355200, 355 Series, 3-Phase Voltage/Phase Monitor, Voltage Asymmetry, Voltage Sensing AC 190 ~ 240VAC, SPDT (1 Form C)

In stock
SKU: 355200
Regular price $562.92
Rated voltage
Phase
Contact
⚠️ IMPORT NOTICE
FOR ALL ORDERS OUTSIDE CANADA, CUSTOMERS ARE RESPONSIBLE FOR ANY IMPORT DUTIES, TARIFFS, TAXES, AND CUSTOMS FEES THAT MAY APPLY TO THEIR ORDERS.

Use this text to encourage communication or promote sharing on social networks.

You can also add links

The 355 series is a three-phase voltage monitor with adjustable trip and restart delay, adjustable voltage unbalance, and multiple diagnostic lights. It is ideal for heavy-duty applications that need both protection and simple user-friendly diagnostics. Suitable applications include pump panels, commercial HVAC, oil rigs, and many more. The 355 series uses microcontroller technology to monitor incoming voltage and de-energize its output relay if power problems exist. It can protect motors from damage caused by single-phasing, high- and low-voltage, phase reversal, and voltage unbalance. These relays have four diagnostic LEDs that clearly show overvoltage, undervoltage, voltage unbalance, reverse-phase, and normal conditions. The adjustable trip and restart settings prevent nuisance tripping due to rapidly fluctuating power line conditions and allow staggered start-up of multiple motors after a fault to prevent a low-voltage condition.

Series 355 models include the 355-200, which is equipped with a heavy-duty 10 A general purpose SPDT relay. The 355- 400 and 355-600 models are equipped with a 470 VA @ 600 V ac pilot duty SPDT relay. A high-voltage (600 V) DPDT relay output option is available with the 400 V model.

Applications

• Pump panels
• Commercial HVAC
• Oil rigs
• Heavy-duty applications that need both protection and simple user-friendly diagnostics

*Note: 50 Hz will increase all delay times by 20%.

Specifications

Input Characteristics  
Line Voltage (Specify voltage range) 355200     190–240 V ac
355400     380–480 V ac
355600     475–600 V ac
Frequency 50*/60 Hz
Functional Characteristics
Low Voltage (% of setpoint) Trip            90% ±1%
Reset         93% ±1%
High Voltage (% of setpoint) Trip           110% ±1%
Reset        107% ±1%
Voltage Unbalance (NEMA) Trip             2–8% adjustable
Reset          Trip setting minus 1%
Trip Delay Time Low & High Voltage and Unbalance      2–30 seconds adjustable
Single-phasing Faults (>25% UB)           2 seconds
Restart Delay Time After a Fault or Power Loss       Manual, 2–300 seconds adjustable
Output Characteristics
Output Contact Rating
SPDT (355200) Pilot Duty                   480 VA at 240 V ac
General Purpose        10 A
SPDT (355400, 355600) Pilot Duty                    470 VA @ 600 V ac
DPDT (-5 Option) Pilot Duty                    470 VA @ 600 V ac
General Characteristics
Temperature Range Operating     -40° to 70 °C (-40° to 158 °F)
Storage         -40° to 80 °C (-40° to 176 °F)
Repeat Accuracy Fixed Conditions                     ±0.1%
Maximum Input Power           6 W
Terminal Torque 7 in.-lbs.
Wire Size 12–18 AWG
Transient Protection (Internal) 2500 V for 10 ms
Dimensions H 74.42 mm (2.93”)
W 133.86 mm (5.27”)
D 74.93 mm (2.95”)
Weight 0.94 lb. (15.04 oz., 426.38 g)
Mounting Method #8 screws
Special Options Option 5 - DPDT Relay
Certification & Compliance UL      UL 508 (File #E68520)