Littelfuse 455480R, 455 Series, 3-Phase Voltage/Phase Monitor, Voltage Asymmetry, Voltage Sensing AC 380 ~ 480VAC, SPDT (1 Form C)

In stock
SKU: 455480R
Regular price $562.92
Rated voltage
Phase
Description

Use this text to encourage communication or promote sharing on social networks.

You can also add links

The 455 series is a three-phase, dual-range voltage monitor that combines load and line side monitoring for a complete protection solution. Load side monitoring alerts the user to contactor failure or impending contactor failure. Line side monitoring protects the motor from damaging fault conditions that may be present prior to the motor starting. This is unique because with other line/load side monitors, the motor must be started before a voltage fault is detected. With the 455 series, the motor is fully protected at all times.

This voltage monitor protects 190–480 V ac, 50*/60 Hz motors regardless of their size. It automatically selects between the 200 V and 400 V range when the user selects the nominal voltage setpoint. Other adjustments include a 2–30 second trip delay, a 2–300 second restart delay (and manual restart), and a voltage unbalance trip point of 2–8%. The voltage monitor’s circuitry is powered through the line side connections so there is no need for separate control power, making it easy to install.

Equipped with an infrared LED, the 455 series can communicate with the optional hand-held diagnostic tool, Informer-MS, to obtain valuable information such as real-time voltage, voltage unbalance on both line and load sides, motor run hours, last 20 faults, last 32 motor starts, high- and low-voltage trip points, voltage unbalance trip point, restart and trip delay settings, LED status, and more

 Applications

• Oil rigs
• Compressors and fan motors
• HVAC
• Heat, well, and sump pumps
• Small conveyer motors

Note: 50 Hz will increase all delay times by 20%

Specifications

Input Characteristics  
Frequency 50*/60 Hz
Functional Characteristics
Low Voltage (% of setpoint) Trip            90% ±1%
Reset         93% ±1%
High Voltage (% of setpoint) Trip            110% ±1%
Reset         107% ±1%
Voltage Unbalance (NEMA) Trip            2 –8% adjustable
Reset         Trip setting minus 1%
Trip Delay Time Low & High Voltage and Unbalance          2–30 seconds adjustable
Single-phasing Faults (>25% UB)               2 seconds fixed
Restart Delay Time After a Fault                  Manual, 2–300 seconds adjustable
After a Complete Power Loss      Manual, 2–300 seconds adjustable
After a Motor Shut-down            Manual, 2–300 seconds adjustable
Output Characteristics
Output Contact Rating (SPDT) Pilot Duty                480 VA @ 240 V ac
General Purpose     10 A
High Voltage Relay (-480R) Pilot Duty                 470 VA @ 600 V ac
General Characteristics
Ambient Temperature Range Operating              -40° to 70 °C (-40° to 158 °F)
Storage                  -40° to 80 °C (-40° to 176 °F)
Repeat Accuracy Fixed Conditions ±0.1%
Maximum Input Power 6 W
Terminal Torque 7 in.-lbs.
Wire Size 12–18 AWG
Transient Protection (Internal) IEC 61000-4-5;1995 ±6 kV
Dimensions H 74.4 mm (2.93”)
W 133.9 mm (5.27”)
D 74.9 mm (2.95”)
Weight 1.1 lbs. (17.6 oz., 498.95 g)
Mounting Method #8 screws
Certification & Compliance UL               UL 508 (File #E68520)
CSA             C22.2 No. 14 (File #46510)
CE                IEC 60947-6-2