Littelfuse 460-100-SP, 460-SP Series, Single-phase voltage monitor, Voltage Sensing AC 95 ~ 120VAC
FOR ALL ORDERS OUTSIDE CANADA, CUSTOMERS ARE RESPONSIBLE FOR ANY IMPORT DUTIES, TARIFFS, TAXES, AND CUSTOMS FEES THAT MAY APPLY TO THEIR ORDERS.
Couldn't load pickup availability
Use this text to encourage communication or promote sharing on social networks.
The 460-100-SP is used on 95–120 V ac, 50*/60 Hz single-phase motors and the 460-200-SP is used on 190–240 V ac, 50*/60 Hz single-phase motors to protect them from damaging high and low voltage conditions. An adjustment knob allows the user to set a 1–500 second restart delay. The variable restart delay is also a power-up delay and can be utilized to stagger-start motors on the same system.
A unique microcontroller-based, voltage-sensing circuit constantly monitors the voltage to detect harmful power line conditions. When a harmful condition is detected, the MotorSaver’s output relay is deactivated after a specified trip delay. The output relay reactivates after power line conditions return to an acceptable level and a specified amount of time has elapsed (restart delay). The trip delay prevents nuisance tripping due to rapidly fluctuating power line conditions.
Features
Proprietary microcontroller-based circuitry
Fixed trip delay 4 seconds
Adjustable restart delay (1–500 s)
Advanced LED indication
DIN-rail or surface-mountable
*Note: 50 Hz will increase all delay timers by 20 %
Pre-order 6-8 Weeks
Specifications
| Input Characteristics | |
| Line Voltage |
460-100-SP : 95–120 V ac 460-200-SP : 190–240 V ac |
| Frequency | 50*/60 Hz |
| Functional Characteristics | |
| Low Voltage (% of setpoint) |
Trip 90 % ±1 % Reset 93 % ±1 % |
| High Voltage (% of setpoint) |
Trip 110 % ±1 % Reset 107 % ±1 % |
| Trip Delay Time | Low or High Voltage: 4 seconds fixed |
| Restart Delay Time |
After a Fault: 1–500 seconds adjustable After a Complete Power Loss: 1–500 seconds adjustable |
| Output Characteristics | |
| Output Contact Rating (1 Form C) |
Pilot Duty 480 VA @ 240 V ac, B300 General Purpose 10 A @ 240 V ac |
| General Characteristics | |
| Ambient Temperature Range |
Operating: -40° to 70°C (-40° to 158°F) Storage: -40° to 80°C (-40° to 176°F) |
| Maximum Input Power | 6 W |
| Class of Protection | IP20, NEMA 1 (finger safe) |
| Relative Humidity | 10–95%, non-condensing per IEC 68-2-3 |
| Terminal Torque | 4.5 in.-lbs. |
| Wire Type | Stranded or solid 12–20 AWG, one per termina |
| Standards Passed | |
| Electrostatic Discharge (ESD) | IEC 61000-4-2, Level 3, 6 kV contact, 8 kV air |
| Radio Frequency Immunity, | Radiated 150 MHz, 10 V/m |
| Fast Transient Burst | IEC 61000-4-4, Level 3, 3.5 kV input power and controls |
| Surge | |
| IEC | IEC 61000-4-5, Level 3, 4 kV line-to-line; Level 4, 4 kV line-to-ground |
| ANSI/IEEE | C62.41 Surge and Ring Wave Compliance to a level of 6 kV line-to-line |
| Hi-potential Test | Meets UL 508 (2 x rated V +1000 V for 1 min) |
| Safety Marks | UL UL 508 (File #E68520) |
| Enclosure | Polycarbonate |
| Dimensions |
H 88.9 mm (3.5”) W 52.93 mm (2.084”) D 59.69 mm (2.35”) |
| Weight | 0.9 lb. (14.4 oz., 408.23 g) |
| Mounting Method | 35 mm DIN rail or Surface Mount (#6 or #8 screws) |