Littelfuse 460-200-SP, 460-SP Series, Single-phase voltage monitor, Voltage Sensing AC 190 ~ 240VAC

In stock
SKU: 460-200-SP
Regular price $219.29
Rated voltage
Phase
⚠️ IMPORT NOTICE
FOR ALL ORDERS OUTSIDE CANADA, CUSTOMERS ARE RESPONSIBLE FOR ANY IMPORT DUTIES, TARIFFS, TAXES, AND CUSTOMS FEES THAT MAY APPLY TO THEIR ORDERS.

Use this text to encourage communication or promote sharing on social networks.

You can also add links

The 460-100-SP is used on 95–120 V ac, 50*/60 Hz single-phase motors and the 460-200-SP is used on 190–240 V ac, 50*/60 Hz single-phase motors to protect them from damaging high and low voltage conditions. An adjustment knob allows the user to set a 1–500 second restart delay. The variable restart delay is also a power-up delay and can be utilized to stagger-start motors on the same system.

A unique microcontroller-based, voltage-sensing circuit constantly monitors the voltage to detect harmful power line conditions. When a harmful condition is detected, the MotorSaver’s output relay is deactivated after a specified trip delay. The output relay reactivates after power line conditions return to an acceptable level and a specified amount of time has elapsed (restart delay). The trip delay prevents nuisance tripping due to rapidly fluctuating power line conditions.

Features
Proprietary microcontroller-based circuitry
Fixed trip delay 4 seconds
Adjustable restart delay (1–500 s)
Advanced LED indication
DIN-rail or surface-mountable

*Note: 50 Hz will increase all delay timers by 20 %

 Specifications

Input Characteristics  
Line Voltage 460-100-SP :    95–120 V ac
460-200-SP :    190–240 V ac
Frequency 50*/60 Hz
Functional Characteristics
Low Voltage (% of setpoint) Trip       90 % ±1 %
Reset    93 % ±1 %
High Voltage (% of setpoint) Trip       110 % ±1 %
Reset     107 % ±1 %
Trip Delay Time Low or High Voltage:   4 seconds fixed
Restart Delay Time After a Fault:       1–500 seconds adjustable
After a Complete Power Loss: 1–500 seconds adjustable
Output Characteristics
Output Contact Rating (1 Form C) Pilot Duty              480 VA @ 240 V ac, B300
General Purpose   10 A @ 240 V ac
General Characteristics
Ambient Temperature Range Operating:   -40° to 70°C (-40° to 158°F)
Storage:       -40° to 80°C (-40° to 176°F)
Maximum Input Power 6 W 
Class of Protection IP20, NEMA 1 (finger safe)
Relative Humidity 10–95%, non-condensing per IEC 68-2-3
Terminal Torque 4.5 in.-lbs.
Wire Type Stranded or solid 12–20 AWG, one per termina
Standards Passed
Electrostatic Discharge (ESD) IEC 61000-4-2, Level 3, 6 kV contact, 8 kV air
Radio Frequency Immunity, Radiated                150 MHz, 10 V/m
Fast Transient Burst IEC 61000-4-4, Level 3, 3.5 kV input power and controls
Surge
IEC IEC 61000-4-5, Level 3, 4 kV line-to-line; Level 4, 4 kV line-to-ground
ANSI/IEEE C62.41 Surge and Ring Wave Compliance to a level of 6 kV line-to-line
Hi-potential Test Meets UL 508 (2 x rated V +1000 V for 1 min)
Safety Marks UL       UL 508 (File #E68520)
Enclosure Polycarbonate
Dimensions H 88.9 mm (3.5”)
W 52.93 mm (2.084”)
D 59.69 mm (2.35”)
Weight 0.9 lb. (14.4 oz., 408.23 g)
Mounting Method 35 mm DIN rail or Surface Mount (#6 or #8 screws)