Littelfuse 777-ACCUPOWER, 777 ACCUPOWER Series, 3-Phase Current & Voltage Monitor, 190-480VAC
Couldn't load pickup availability
Use this text to encourage communication or promote sharing on social networks.
The 777 AccuPower is a fully-programmable, 3-phase motor and pump protection relay. It allows for entry of motor hp rating, full-load amperes, efficiency, and power factors, and will then accurately calculate motor output power. The 777 AccuPower relay is most useful with mag-drive pumps or process applications where the process power is desired over the utility power. Voltage, current, and power measurements can be displayed as well as fault information and setpoints. The built-in display simplifies troubleshooting and allows the user to easily and precisely configure setpoints.
The 777 AccuPower can be used with the optional COM 4-20 output communication module to give an analog signal proportional to output shaft power. Other optional accessories include the RS485MS-2W comms module; the RM1000 remote monitor; and the RM2000 remote monitor. See the accessories products for complete information.
Applications
• For use with mag-drive pumps or process applications where the process power is desired over the utility power
Pre-order 6-8 Weeks
Specifications
Input Characteristics | |
Line Voltage | 200-480 V ac |
Frequency | 50/60 Hz |
Motor Full Load Amp Range |
2-800 A (external CTs required over 90 A) 2 - 25: 3 phase (looped conductors required) |
Functional Characteristics | |
TC- Overcurrent Trip Class | 5, 10, 15, 20, 30 (J prefix enables jam protection feature) |
Output Characteristics | |
Output Contact Rating (SPDT - Form C) |
Pilot duty 480 VA @ 240 V ac General Purpose 10 A @ 240 V ac |
General Characteristics | |
Ambient Temperature Range |
Operating -40 °C to 70 °C (-40 °F to 158 °F) Storage -40 °C to 80 °C (-40 °F to 176 °F) |
Accuracy | |
Measured Horsepower/Kilowatt |
Typical ±3 %* Voltage ±1 % Current ±3 %(<100 amps direct) GF Current ±15 % Timing 5 % ±1 second |
Repeatability |
Voltage ±0.5 % of nominal voltage Current ±1 % (<100 amps direct) Maximum Input Power 10 W Pollution Degree 3 Class of Protection IP20, NEMA 1 (finger safe) Relative Humidity 10-95 %, non-condensing per IEC 68-2-3 Terminal Torque 7 in.-lbs. |
Standards Passed | |
Electrostatic Discharge | (ESD) IEC 61000-4-2, Level 3, 6 kV contact, 8 kV air |
Radio Frequency Immunity (RFI) |
Conducted IEC 61000-4-6, Level 3 10 V/m Radiated IEC 61000-4-3, Level 3 10 V/m |
Fast Transient Burst | IEC 61000-4-4, Level 3, 3.5 kV input power |
Short Circuit Rating | 100 kA |
Surge | |
IEC | 61000-4-5 Level 3, 2 kV line-to-line; Level 4, 4 kV line-to-ground |
ANSI/IEEE | C62.41 Surge and Ring Wave Compliance to a level of 6 kV line-to-line |
Hi-Potential Test | Meets UL 508 (2 x rated V + 1000 V for 1 min.) |
Vibration | IEC 68-2-6, 10-55 Hz, 1 mm peak-to-peak, 2 hrs, 3 axis |
Shock | IEC 68-2-27, 30 g, 3 axis, 11 ms duration, half-sine pulse |
Max. Conductor Size through 777 | 0.65” with insulation |
Dimensions |
H 77.47 mm (3.05”) W 97.79 mm (3.85”) D 128.27 mm (5.05”) |
Weight | 1.3 lbs. (20.8 oz., 589.67 g) |
Mounting Method Surface mount | Surface mount (4 - #8 screws) or DIN-rail mount |
Certification & Compliance |
UL UL 508, UL 1053 CE IEC 60947-1, IEC 60947-5-1 CSA C22.2 |