Littelfuse 777-HVR-SP, 77C Series, Single-Phase Current & Voltage Monitor, 100-240VAC, 2-800A (external CTs required above 90A), Provides 470VA @ 600 V ac output SPDT relay contacts. For systems with no control power transformer
Pickup available at 220 Alden Road
Usually ready in 24 hours
Use this text to encourage communication or promote sharing on social networks.
The single-phase 77C unit is a fully-programmable, electronic overload relay designed to protect any motor drawing 2-800 full load A (external CTs are required above 90 A). Common applications include conveyor systems, HVAC equipment, saws and grinders, fan motors, and almost any pumping application. The 77C and 777-HVR-SP (family of products) are for single-phase 100-240 V ac applications.
All of the overload relays provide unsurpassed protection by combining overload, underload, and voltage in one unit. For standalone applications, the units incorporate a 3-digit LED display that is used for programming, providing real-time operational information, and displaying diagnostic codes to aid in troubleshooting a fault condition. These units also feature a communications network port that can be used with communication modules, listed in the 777 accessories section, to form a Modbus, DeviceNet™, Profibus, or Ethernet network. Up to 99 units can be remotely monitored and controlled from a PC, PLC, or SCADA system, and data logging through a PC with the optional Solutions software. This capability allows for a simple, cost-effective way to meet new requirements for arc-flash safety.
Applications
• Conveyor systems
• HVAC equipment
• Saws and grinders
• Fan motors
Pre-order 6-8 Weeks
Specifications
Functional Characteristics | |
Frequency | 50/60 Hz |
TC- Overcurrent Trip Class (77C, 777 non-Plus Series units) | 5, 10, 15, 20, 30 (J prefix enables jam protection feature) |
Output Characteristics | |
Output Contact Rating (SPDT - Form C) |
Pilot duty rating 480 VA @ 240 V ac, B300 General purpose 10 A @ 240 V ac Pilot duty rating for HVR models 470 VA @ 600 V ac, B600 |
General Characteristics | |
Ambient Temperature Range |
Operating -20 °C to 70 °C (-4 °F to 158 °F) Storage -40 °C to 80 °C (-40 °F to 176 °F) |
Accuracy |
Voltage ±1 % Current ±3 %(<100 amps direct) GF Current ±15 % |
Timing (77C, 777 non-Plus Series units) | 5 % +1 second |
Repeatability | |
Voltage | ±0.5 % of nominal voltage |
Current | ±1 % (<100 amps direct) |
Maximum Input Power | 10 W |
Pollution Degree | 3 |
Class of Protection | IP20 |
Relative Humidity | 10-95 %, non-condensing per IEC 68-2-3 |
Terminal Torque | 7 in.-lbs |
Standards Passed | |
Electrostatic Discharge (ESD) | IEC 61000-4-2, Level 3, 6 kV contact, 8 kV air |
Radio Frequency Immunity (RFI) |
Conducted IEC 61000-4-6, Level 3 10 V/m Radiated IEC 61000-4-3, Level 3 10 V/m |
Fast Transient Burst | IEC 61000-4-4, Level 3, 3.5 kV input power |
Short Circuit | 100 kA |
Surge | |
IEC | 61000-4-5, Level 3, 2 kV line-to-line; Level 4, 4 kV line-to-ground |
ANSI/IEEE | C62.41 Surge and Ring Wave Compliance to a level of 6 kV line-to-line |
Hi-potential Test | Meets UL 508 (2 x rated V +1000V for 1 minute) |
Vibration | IEC 68-2-6, 10-55 Hz, 1 mm peak-to-peak, 2 hours, 3 axis |
Shock | IEC 68-2-27, 30 g, 3 axis, 11 ms duration, half-sine pulse |
Maximum Conductor Size (with insulation) through 77C | 0.65” |
Dimensions |
H 77.47 mm (3.05”) W 97.79 mm (3.85”) D 128.27 mm (5.05”) |
Weight | 1.56 lbs. (24.96 oz., 707.6 g) |
Mounting Method | Surface mount (4 - #8 screws) or DIN rail mount |
Certification & Compliance |
UL UL 508, UL 1053 (File #E68520) CE IEC 60947-1, IEC 60947-5-1 CSA C22.2 |