The 77C-KW single-phase relay is part of the 777/77C product family. The 77C-KW, 77C-KW/HP and 77C-LR-KW/HP are fully programmable pump protection relays that monitor for high or low voltage and overload and underload conditions based on power. These overload relays are designed to protect any motor drawing 2–800 full load A (external CTs are required above 90 A). The 777-HVR-SP and 77C are for single-phase 100–240 V ac applications.

All of the overload relays provide unsurpassed protection by combining overload, underload, and voltage in one unit. For standalone applications, the units incorporate a 3-digit LED display that is used for programming, providing real-time operational information, and displaying diagnostic codes to aid in troubleshooting a fault condition.

The units also feature a network communications port that can be used with communication modules, listed in the 777 accessories section, to form a Modbus*, DeviceNet™, Profibus, or Ethernet network. Up to 99 units can be remotely monitored and controlled from a PC, PLC, or SCADA system, and data logging through a PC with the optional Solutions software. This capability allows for a simple, cost-effective way to meet new requirements for arc-flash safety.

The underpower trip feature is desirable anytime the current vs. load characteristic is non-linear or has little change. In general terms, smaller motors and slow-speed motors have little change in current over the normal load range. Larger motors that are running light loads will also show small current changes over the operating load range. Common uses include pumping applications where motors run slower than 3400 rpm and usually have small current versus load changes, such as slow speed mixers or agitator motors up to 50 hp, mag-drives, or can pumps.

Note: The Littelfuse PumpSaver® relay provides the high sensitivity of a power monitor to protect pump motors from dry run and dead head conditions.

Applications
• Conveyor systems
• HVAC equipment
• Saws and grinders
• Fan motors

Specifications

Input Voltage  100–240 V ac, 1Ø
Frequency 50–60 Hz
Motor Full Load Amp Range
77C-KW/HP 2–25 A (loops required); 26–90 A (direct); 91–800 A (external CTs)
77C-LR-KW/HP 1.0 A - 2.0 A (additional loop); 2.0 A - 9.0 A (direct)
Short Circuit Withstand Rating 100 kA per UL and CSA
Power Consumption 5 W (Maximum)
Output Contact Rating SPDT (Form C) Pilot duty rating:    480 VA @ 240 V ac
General purpose:   10 A @ 240 V ac
Expected Life Mechanical      1 x 106 operations
Electrical          1 x 105 operations at rated load
Accuracy at 25 °C (77 °F) Voltage            ±1 %
Current            ±3 % (Direct, No External CTs)
Timing             5 % ± 1 second
Repeatability Voltage            ± 0.5 % of nominal voltage
Current            ± 1 % (Direct, No External CTs)
Standards Passed
Electrostatic Discharge (ESD) IEC 61000-4-2, Level 3, 6 kV contact, 8 kV air
Radio Frequency Immunity (RFI) Conducted       IEC 61000-4-6, Level 3 10 V/m
Radiated           IEC 61000-4-3, Level 3 10 V/m
Fast Transient Burst IEC 61000-4-4, Level 3, 3.5 kV input power
Surge
IEC IEC 61000-4-5, Level 3, 2 kV line-to-line; Level 4, 4 kV line-to-ground
ANSI/IEEE C62.41 Surge and Ring Wave compliance to a level of 6 kV line-to-line
Hi-potential Test Meets UL 508 (2 x rated V +1000 V for 1 min.)
Vibration IEC 68-2-6, 10-55 Hz, 1 mm peak-to-peak, 2 hours, 3 axis
Shock IEC 68-2-27, 30 g, 3 axis, 11 ms duration, half-sine pulse
Mechanical
Dimensions H 78.74 mm (3.1”)
W 99.06 mm (3.9”)
D 129.54 mm (5.1”)
Terminal Torque 7 in.-lbs.
Enclosure Material Polycarbonate
Weight 1.2 lbs
Maximum Conductor Size Through 777 0.65” with insulation
Environmental
Temperature Range Ambient Operating   -20 °C–70° C (-4 °F–158 °F)
Ambient Storage       -40 °C–80° C (-40 °F–176 °F)
Pollution Degree 3
Class of Protection IP20, NEMA 1
Relative Humidity 10–95 %, non-condensing per IEC 68-2-3
Programmable Operating Points Range
LV- Low Voltage Threshold 85 V - HV Setting
HV- High Voltage Threshold 264 V - LV Setting
MULT- # of Conductors or CT Ratio (XXX:5) 77C:          1–10 Conductors or 100-800 Ratio
77C-LR:     1 or 2
OC- Overcurrent Threshold (20–100 A) ÷ MULT or 80–120 % of CT Primary
TC- Overcurrent Trip Class* 5, J5, 10, J10, 15, J15, 20, J20, 30, J30, or LIn (linear)
RD1- Rapid Cycle Timer 0, 2–500 seconds
RD2- Restart Delay After All Faults Except Undercurrent (motor cool down timer)** 2–500 minutes/seconds
RD3- Restart Delay After Undercurrent (dry well recovery timer) 2–500 minutes/seconds
#RU- Number of Restarts
After Undercurrent 0, 1, 2, 3, 4, A (Automatic)
ADDR- RS485 Address A01- A99
#RO-Number of Restarts
After Overcurrent 0, 1, 2, 3, 4, A (Automatic)
LP/PWS (PWS = LP Range) 1 = 0.01 - 0.99 KW
2 = 1.00 - 9.95 KW
3 = 10.0 - 99.5 KW
4 = 100 - 650 KW
5 = 0.01 - 1.30 HP
6 = 1.34 - 13.3 HP
8 = 13.4 - 133 HP
9 = 134 - 871 HP
Certification & Compliance UL         UL508, UL1053 (File #E68520)
CSA      C22.2