Littelfuse ALT-200-3-SW, ALT Pump Controls Series, Alternating Relay DPDT, 190-240VAC, 8-pin Octal Mounting
FOR ALL ORDERS OUTSIDE CANADA, CUSTOMERS ARE RESPONSIBLE FOR ANY IMPORT DUTIES, TARIFFS, TAXES, AND CUSTOMS FEES THAT MAY APPLY TO THEIR ORDERS.
Couldn't load pickup availability
Use this text to encourage communication or promote sharing on social networks.
The ALT-xxx-3-SW Series are used to alternate between two loads and are commonly used in duplex pump-up and pump-down applications to balance the runtime of both pumps.
The ALT relays have a built-in debounce time delay that prevents the relay from changing state if the float momentarily bounces, and they have a built-in switch to manually force a specific load (pump) to operate each time the input float closes. This is helpful when performing periodic maintenance or pump repair.
Must use the OT08PC socket for the 8-pin models, and the OT11PC socket for the 11-pin models, for UL Rating!
*Note: Manufacturer’s recommended screw terminal torque for the OT Series Octal
The sockets can be surface mounted or installed on DIN Rail Sockets is 12 in.-lbs
Pre-order 6-8 Weeks
| Input Characteristics | |
| Supply Voltage | 190-240VAC |
| Frequency | 50/60Hz |
| Functional Characteristics | |
| Debounce Time Delay | |
| ALT-100-1-SW | 1 second |
| ALT-100-3-SW, ALT-200-3-SW | 5 seconds |
| Output Characteristics | |
| Output Relay (DPDT) |
Pilot Duty 480VA @ 240VAC General Purpose 10A @ 240VAC |
| General Characteristics | |
| Temperature Range | -40° to 70°C (-40° to 158°F) |
| Maximum Input Power | 5 W |
| Standards Passed | |
| Electrostatic Discharge (ESD) | IEC 61000-4-2, Level 3, 6kV contact, 8kV air |
| Radio Frequency, Radiated | 150MHz, 10V/m |
| Fast Transient Burst | IEC 61000-4-4, Level 3, 3.5kV input power and controls |
| UL (OT08PC or OT11PC octal socket required) | UL508 (File #E68520) |
| CE | IEC 60947-6-2 |
| Dimensions |
H 44.45 mm (1.75”) W 60.33 mm (2.375”) D 104.78 mm (4.125”) (with socket) |
| Weight | 0.65 lb. (10.4 oz., 294.84 g) |
| Mounting Method | DIN rail or surface mount (plug into OT08PC or OT11PC socket) |
| Sockets Available |
Model OT08PC UL Rating 600V Model OT11PC UL Rating 300V |