Littelfuse DLMUBRAAA, DLM Series, Voltage Asymmetry, Voltage Sensing AC, Phase Loss 200 ~ 480VAC, SPDT (1 Form C)

In stock
SKU: DLMUBRAAA
Regular price $495.19
Rated voltage
Restart function

Use this text to encourage communication or promote sharing on social networks.

You can also add links

The DLMU Series is a universal voltage, 3-phase voltage monitor. It continuously measures the voltage of each of the three phases with microcontroller accuracy and compares the value to preset trip points. It separately senses phase reversal and loss; over, under and unbalanced voltages; and over or under frequency. Protection is assured during periods of large average voltage fluctuations or when regenerated voltages are present. The unit trips within 200ms when phase loss is detected. Adjustable time delays are included to prevent nuisance tripping and short cycling of sensitive equipment. The isolated, 10A, SPDT and 2A alarm output relay contacts trip when a phase voltage exceeds the trip limits for the trip delay. Nominal line voltage, voltage unbalance, and time delays are knob adjustable. The phase loss setpoint and the acceptable frequency range are fixed. Both delta and wye systems can be monitored; no connection to neutral is required.

Operation

Upon application of line voltage, the output is de-energized and the restart delay begins. If all the 3-phase voltages are within the acceptable range, the output energizes at the end of the restart delay. The microcontroller circuitry automatically senses the voltage range, and selects the correct operating frequency (50 or 60Hz). The over and undervoltage trip points are set automatically. When the measured value of any phase voltage exceeds the acceptable range limits (lower or upper) the trip delay begins. At the end of the trip delay the output relay de-energizes. If the phase voltage returns to an acceptable value before the trip delay expires, the trip delay is reset and the output remains energized. Under, over, and unbalanced voltages plus over or under frequency must be sensed for the complete trip delay before the unit trips. The unit trips in 200ms when phase loss or reversal are sensed. The unit will not energize if a fault is sensed as the line voltage is applied. Reset:

Reset is automatic upon correction of the voltage or frequency fault or phase sequence.

Specifications

Line Voltage  
Type         3-phase delta or wye with no connection to neutral
Operating Voltage  
200-480VAC                  Voltage              Line           LineVoltage
Range    Adj.Range         Frequency         Max.
240        200-240VAC       50/60Hz
380        340-420VAC         50Hz
480        400-480VAC         60Hz              550VAC
600VAC 600        500-600VAC        50/60Hz         600VAC
AC Line Frequency 50/60 Hz automatically detected
Phase Loss ≥ 25% unbalance
Response Time ≤200ms
Undervoltage & Voltage Unbalance
Type Voltage detection with delayed trip & automatic reset
Overvoltage
TripVoltage 109 - 113% of the adjusted line voltage
Reset Voltage ≅ -3% of the trip voltage
Undervoltage
Trip Voltage 88 - 92% of the adjusted line voltage
Reset Voltage ≅ +3% of the trip voltage
Voltage Unbalance Adjustable 2 - 10% or specify fixed unbalance of 2 - 10% in 1% increments
Reset on balance ≅ -0.7% unbalance
Trip Delay
Active On Over/undervoltage, voltage unbalance, over/ under frequency
Range Adjustable from 1 - 30s or specify fixed delay 1 - 30s in 1s increments
Tolerance ± 15%
Restart Delay
Range Adjustable from 0.6 - 300s; if no restart delay is selected a 0.6s initialization delay applies
Tolerance ± 15%
Over/Under Frequency ±4%; Reset ±3%; 50/60 Hz
Phase Sequence A, B, C, L1, L2, L3
Response Time -Phase Reversal & Phase Loss ≤200 ms
Reset Automatic
Output
Type Isolated Electromechanical Relay
Form C Isolated, SPDT
Form C Rating 10A resistive @ 240VAC;
8A resistive @ 277VAC; NO-1/4 hp @ 120VAC;
1/3 hp @ 240VAC
Form A solated, NO, SPST
Form A Rating 2A @ 277VAC
Life Mechanical - 1 x 10⁶ ; Electrical - 1 x 30³
Protection
Phase Reversal/Failure ASME A17.1 Rule 210.6
Motors and Generators NEMA MG1 14:30, 14:35
Surge IEEE C62.41-1991 Level B
Isolation Voltage ≥ 2500V RMS input to output
Mechanical
Mounting Surface mount with 2 #8 (M4 x 0.7) screw or snap on 35mm DIN Rail
Note: 0.25 in.(6.35 mm) spacing between units or other devices is required
Dimensions H 110 mm (4.33”)
W 75 mm (2.95”)
D 50 mm (1.97”)
Termination Screw terminals with captive wire clamps for up to #14 AWG (2.5 mm2 ) wire
Terminal Torque 4.4 in.-lbs.
Environmental
Operating/Storage Temperature -40° to 60°C / -40° to 85°C
Humidity 95% relative, non-condensing
Weight ≅ 8.6 oz (244 g)