Littelfuse ECS2HBC, ECS Series, Current Sensors, Current Sensing AC 24VAC, SPDT (1 Form C)

In stock
SKU: ECS2HBC
Regular price $266.09
Rated voltage
Ampere rating
Trip delay

Use this text to encourage communication or promote sharing on social networks.

You can also add links

The ECS Series of single-phase AC current sensors is a universal, overcurrent or undercurrent sensing control. Its built-in toroidal sensor eliminates the inconvenience of installing a stand-alone current transformer. Includes onboard adjustments for current sensing mode, trip point, and trip delay. Detects over or undercurrent events like locked rotor, loss of load, an open heater or lamp load, or proves an operation is taking place or has ended.

Operation

Input voltage must be supplied at all times for proper operation. When a fault is sensed throughout the trip delay, the output relay is energized. When the current returns to the normal run condition or zero, the output and the delay are reset. If a fault is sensed and then corrected before the trip delay is completed, the relay will not energize and the trip delay is reset to zero.

Features & Benefits

Built-in toroidal current sensing Eliminates need to install stand-alone current transformer and provides isolation from monitored circuit
Encapsulated  Protects against shock, vibration, and humidity
Adjustable mode, trip point and trip delay Provides flexibility for use in many applications
10A, SPDT isolated relay output Allows control of AC voltage loads

Specifications

Sensor  
Type Toroidal through hole wiring
Mode Over or undercurrent, switch selectable on the unit or factory fixed
Trip Point Range 0.5 - 50A in 3 adjustable ranges or fixed
Tolerance Adjustable Guaranteed range
Fixed 0.5 - 25A: 0.5A or ±5% whichever is less; 26 - 50A: ±2.5%
Maximum Allowable Current Steady – 50A turns;
Inrush – 300A turns for 10s
Trip Point Hysteresis ≅ ±5%
Trip Point vs. Temperature ±5%
Response Time ≤ 75ms
Frequency 45/500 Hz
Type of Detection Peak detection
Trip Delay
Type Analog
Range Adjustable 0.150 - 7s; 0.5 - 50s (guaranteed ranges)
Factory Fixed +/- 10%
Delay vs. Temperature ±15%
Sensing Delay on Startup Factory fixed 0 - 6s: +40%, -0%
Input
Voltage 24 VAC; 24VDC
Tolerance 12VDC & 24VDC/AC: -15 - 20%
AC Line Frequency 50/60 Hz
Output
Type Electromechanical relay
Form Isolated, SPDT
Rating 10A resistive @ 240VAC; 1/4 hp @ 125VAC;
1/2 hp @ 250VAC
Life Mechanical – 1 x 106 ; Electrical – 1 x 105
Protection
Circuitry Encapsulated
Isolation Voltage ≥ 2500V RMS input to output
Insulation Resistance ≥ 100 MΩ
Mechanical
Mounting Surface mount with two #6 (M3.5 x 0.6) screws
Dimensions H 88.9 mm (3.5”);
W 63.5 mm (2.5”);
D 44.5 mm (1.75”)
Termination 0.25 in. (6.35 mm) male quick connect terminals (5)
Environmental
Operating/Storage Temperature -40° to 60°C / -40° to 85°C
Humidity 95% relative, non-condensing
Weight ≅ 6.4 oz (181 g)