Littelfuse ECSW4MBHT, ECSW Series, Current Sensors, Current Sensing AC 120VAC, SPDT (1 Form C)

In stock
SKU: ECSW4MBHT
Regular price $384.76
Rated voltage
Ampere rating
Trip delay; Sensing delay on startup

Use this text to encourage communication or promote sharing on social networks.

You can also add links

The ECSW Series of single-phase, AC window, current sensors includes adjustable overcurrent and undercurrent trip points. Detects locked rotor, jam, loss of load, an open heater or lamp load, a broken belt, or loss of suction. LED’s aid in trip point adjustment and provide fault indication. The built-in toroidal sensor eliminates the need for an external current transformer. The output can be electrically latched after a fault, or automatically reset. Remote resetting of a latched output by removing input voltage. The unit includes switch selectable zero current detection and normally de-energized or energized output operation. Time delays are included to improve operation and eliminate nuisance tripping

Features & Benefits

Built-in toroidal current sensing Eliminates need to install stand alone current transformer and provides isolation from monitored circuit
Encapsulated Protects against shock, vibration, and humidity
LED indication Visual indication for trip point adjustment and fault indication
Multiple switch selectable features User selectable zero current detection, latched, normally de-energized, or energized output adds application flexibility
Adjustable trip delay Eliminates nuisance tripping and prevents rapid cycling
Isolated 10A, SPDT output contacts Allows control of loads for AC or DC voltages

Specifications

Sensor  
Type Toroid, through hole wiring for up to #4 AWG (21.1 mm2 ) THHN wire
Mode Over & undercurrent trip points (window current sensing)
Trip Point Range 0.5 - 50A in 3 adjustable ranges
Tolerance Guaranteed range
Maximum Allowable Current Steady - 50A turns; Inrush - 300A turns for 10s
Time Point vs Temp. & Voltage ±5%
Response Time ≤ 75ms
Frequency 45/500 Hz
Type of Detection Peak detection
Zero Current Detection < 250mA turns typical
Trip Delay
Range 0.15 - 50s in 2 adjustable ranges or 0.1 - 50s fixed
Tolerance Adjustable: guaranteed range; Fixed: ±10%
Sensing Delay On Start Up Fixed ≅ 0.1 - 6s in 1s increments
Tolerance +40% -0%
Delay vs. Temp. & Voltage ±15%
Input
Voltage 24, 120, or 230VAC; 12 or 24VDC
Tolerance 12VDC & 24VDC/AC: -15% - 20%
120 & 230VAC: -20% - 10%
AC Line Frequency 50/60 Hz
Output
Type Electromechanical relay
Mode: Switch Selectable ON: Energized during normal operation,
       de-energized after a fault
OFF: De-energized during normal operation,
        energizes during a fault
Form Isolated, SPDT
Rating 10A resistive @ 240VAC; 1/4 hp @ 125VAC;
1/2 hp @ 250VAC
Life Mechanical - 1 x 106 ; Electrical - 1 x 105
Type Electrical
Reset Remove input voltage
Function Switch selectable latching function
Protection
Surge IEEE C62.41-1991 Level A
Circuitry Encapsulated
Isolation Voltage ≥ 2500V RMS input to output
Insulation Resistance ≥ 100 MΩ
Mechanical
Mounting Surface mount with two #6 (M3.5 x 0.6) screws
Dimensions H 88.9 mm (3.5”);
W 63.5 mm (2.5”);
D 44.5 mm (1.75”)
Termination 0.197 in. (5 mm) terminal blocks for up to #12
(3.2 mm2) AWG wire
Environmental
Operating/Storage Temperature -40° to 60°C / -40° to 85°C
Humidity 95% relative, non-condensing
Weight ≅ 6.4 oz (181 g)