Littelfuse EL3100-00, EL3100 Series, Ground-Fault & Phase-Voltage Indicator, 208/600VAC
FOR ALL ORDERS OUTSIDE CANADA, CUSTOMERS ARE RESPONSIBLE FOR ANY IMPORT DUTIES, TARIFFS, TAXES, AND CUSTOMS FEES THAT MAY APPLY TO THEIR ORDERS.
Couldn't load pickup availability
Use this text to encourage communication or promote sharing on social networks.
The EL3100 is a self-powered ground-fault and phasevoltage indication system for 3-phase systems. The EL3100 meets the National Electrical Code (NEC) and the Canadian Electrical Code (CEC) requirements for ground detectors for ungrounded alternating-current systems. Voltage connections are provided on the EL3100 for 208, 240, 480, and 600-V systems. Three green LED’s on the EL3100 indicate the presence of phase-to-ground voltage and one red LED indicates a ground fault. The EL3100 can operate stand-alone or with up to five remote LED indicators. A solid-state relay output provides indication of a ground fault. The output relay is closed when the 3-phase neutral voltage shifts as the result of ground leakage.
Specifications
| Input Voltage |
Input L: 208/240 VAC Input H: 480/600 VAC |
| Dimensions |
H 87.0 mm (3.43”) W 112.5 mm (4.43”) D 56.0 mm (2.2”) |
| Approvals | CSA certified, UL Listed (E340889) |
| Conformally Coated | Standard feature |
| Warranty | 5 years |
| Mounting | DIN, Surface |