Littelfuse ERDI436, Interval Timer Series, 120VAC, Interval Time Delay Relay DPDT (2 Form C) 0.6 Sec ~ 60 Sec Delay 10A @ 120/240VAC Chassis Mount
Pickup available at 220 Alden Road
Usually ready in 24 hours
Use this text to encourage communication or promote sharing on social networks.
Econo-Timers are a combination of digital electronics and an electromechanical relay. DPDT relay output for relay logic circuits, and isolation of input to output voltages. For applications, such as interval on, pulse shaping, minimum run time, etc. The ERD Series is encapsulated to protect the circuitry from shock, vibration and humidity.
Operation (Interval)
Upon application of input voltage, time delay begins, and output relay energizes. At the end of time delay, output de-energizes until input voltage is removed.
Reset: Removing input voltage resets the time delay and the output.
Operation (Single Shot)
Input voltage must be applied before and during timing. Upon momentary or maintained closure of initiate switch, output relay energizes for time delay. At the end of the delay, output de-energizes. Opening or reclosing initiate switch during timing has no affect on time delay. Output will energize if initiate switch is closed when input voltage is applied.
Reset: Reset occurs when time delay is complete & initiate switch is opened. Loss of input voltage resets time delay and output.
Specifications
Time Delay | |
Type | Digital integrated circuitry |
Range |
0.1s - 500m in 11 adjustable ranges, 0.1s - 1000m fixed |
Adjustment | External adjust or onboard |
Repeat Accuracy | ±0.5% |
Tolerance (Factory Calibration) | ≤ ±10% |
Reset Time | ≤ 150ms |
Time Delay vs Temp. & Voltage | ≤ ±2% |
Input | |
Voltage | 120VAC or 230VAC |
Tolerance |
12VDC & 24VDC/AC: -15% - 20% 120VDC/AC & 230VAC: -20% - 10% |
AC Line Frequency | 50/60 Hz |
Output | |
Type | Isolated relay contacts |
Form | DPDT |
Rating |
10A resistive @ 120/240VAC & 28VDC; 1/3 hp @ 120/240VAC |
Life | Mechanical - 1 x 10⁷ ; Electrical - 1 x 10⁶ |
Protection | |
Isolation Voltage | ≥ 1500V RMS input to output |
Insulation Resistance | ≥ 100 MΩ |
Polarity | DC units are reverse polarity protected |
Mechanical | |
Mounting | Surface mount with two #6 (M3.5 x 0.6) screws |
Dimensions |
H 88.9 mm (3.5”); W 63.5 mm (2.5”); D 43.2 mm (1.7”) |
Termination | 0.25 in. (6.35 mm) male quick connect terminals |
Environmental | |
Operating/Storage | |
Temperature | -40° to 65°C / -40° to 85°C |
Weight | ≅ 5.7 oz (162 g) |