Littelfuse HLVA6I23, HLVA Series, Voltage Sensing AC 100 ~ 240VAC, SPDT (1 Form C)

In stock
SKU: HLVA6I23
Regular price $227.33
Rated voltage

Use this text to encourage communication or promote sharing on social networks.

You can also add links

The HLVA6I23 is a single-phase undervoltage monitor designed to protect sensitive equipment from brownout or undervoltage conditions. Time delays are included to prevent nuisance tripping and short cycling. The 30A, 1hp rated, SPDT relay contacts allow direct control of motors, solenoids and valves. The output relay can be ordered with isolated SPDT contact to allow monitoring of one voltage and switching a separate voltage. Two undervoltage trip point ranges allow monitoring of 110 to 120VAC or 208 to 240VAC systems.

Operation

Upon application of input voltage the output relay remains de-energized. When the input voltage value is above the pull-in voltage, the restart delay begins. At the end of the restart delay, the output relay energizes. When the input voltage falls below the trip point, the trip delay begins. If the input voltage remains below the pull-in voltage for the entire trip delay the relay deenergizes. If the input voltage returns to a value above the pull-in voltage, during the trip delay, the trip delay is reset and the relay remains energized. If the input voltage falls below the trip point voltage during the restart delay, the delay is reset and the relay remains de-energized. Reset is automatic upon correction of an undervoltage fault.

Reset: Removing input voltage resets the output relay and the time delays.

Features

. 30A, SPDT, NO output contacts
. 100 to 240VAC input voltage
. 70 to 220VAC adjustable undervoltage trip point in 2 ranges
. Restart delays from 3 - 300s
. Trip delay 1 - 20s fixed
. Isolated or non-isolated relay contacts

 Specifications

Input  
Min & Max RMS Voltage 70 to 264VAC
AC Line Frequency 50/60 Hz
Power Consumption AC ≤ 4VA
Undervoltage Sensing
Type Peak voltage sensing
Ranges (4)  70 to 120VAC
(6)  170 to 220VAC
Pull-In Voltage 105% or trip point voltage
Trip Point Accuracy ± 3% of trip point
Time Delay
Restart Delays 3 - 300s adjustable
Trip Delay 1 - 20s fixed in 1s increments
Repeat Accuracy ±0.5% or 20ms, whichever is greater
Tolerance (Factory Calibration) ±5%
Reset Time ≤ 150ms
Time Delay vs. Temp. & Voltage ≤ ±10%
Output
Type Electromechanical relay
Form SPDT
Ratings                         SPDT-NO      SPDT-NC
General Purpose 125/240VAC        30A             15A
Resistive 125/240VAC        30A              15A
28VDC                  20A              10A
Motor Load 125VAC                1 hp*         1/4 hp**
240VAC                2 hp**        1 hp**
Life Mechanical - 1 x 10⁶
Electrical - 1 x 10⁵, *3 x10⁴, **6,000
Protection
Surge IEEE C62.41-1991 Level A
Circuitry Encapsulated
Isolation Voltage ≥ 1500V RMS input to output; isolated units
Insulation Resistance ≥ 100 MΩ
Mechanical
Mounting Surface mount with one #10 (M5 x 0.8) screw
Dimensions H 76.7 mm (3”)
W 51.3 mm (2”)
D 38.1 mm (1.5”)
Termination 0.25 in. (6.35 mm) male quick connects
Environmental
Operating/Storage Temperature -40° to 60°C / -40° to 85°C
Humidity 95% relative, non-condensing
Weight ≅ 3.9 oz (111 g)