Littelfuse HRDB120, HRDB Series, 12VDC, Off-Delay Time Delay Relay SPDT (1 Form C) 0.1 Sec ~ 10 Sec Delay 30A @ 125/240VAC Chassis Mount
Couldn't load pickup availability
Use this text to encourage communication or promote sharing on social networks.
The HRDB Series combines an electromechanical, relay output with microcontroller timing circuitry. The HRDB offers 12 to 230V operation in five options and factory fixed, external, or onboard adjustable time delays with a repeat accuracy of ±0.5%. The isolated output contact rating allows for direct operation of heavy loads, such as compressors, pumps, blower motors, heaters, etc. The HRDB is ideal for OEM applications where cost is a factor.
Operation (Delay-on-Break)
Input voltage must be applied before and during timing. Upon closure of the initiate switch, the output relay energizes. The time delay begins when the initiate switch is opened. The output remains energized during timing. At the end of the time delay, the output de-energizes. The output will energize if the initiate switch is closed when input voltage is applied.
Reset: Reclosing the initiate switch during timing resets the time delay. Loss of input voltage resets the time delay and output.
Specifications
Time Delay | |
Type | Microcontroller circuitry |
Range | 0.1s - 100m in 5 adjustable ranges or fixed |
Repeat Accuracy | ±0.5 % or 20ms, whichever is greater |
Tolerance (Factory Calibration) | ±1%, ±5% |
Reset Time | ≤ 150ms |
Initiate Time | ≤ 20ms |
Time Delay vs Temp. & Voltage | ≤ ±2% |
Input | |
Voltage |
12VDC & 24VDC: -15% - 20% 24 to 230VAC: -20% - 10% |
Tolerance | ±20% |
AC Line Frequency | 50/60 Hz |
Power Consumption | AC ≤ 4VA; DC ≤ 2W |
Output | |
Type | Electromechanical relay |
Form | Isolated, SPDT |
Ratings | SPDT-NO SPDT-NC |
General Purpose | 125/240VAC 30A 15A |
Resistive |
125/240VAC 30A 15A 28VDC 20A 10A |
Motor Load |
125VAC 1 hp* 1/4 hp** 240VAC 2 hp** 1 hp** |
Life |
Mechanical - 1 x 10⁶ Electrical - 1 x 10⁵, *3 x 10⁴, **6,000 |
Protection | |
Surge | IEEE C62.41-1991 Level A |
Circuitry | Encapsulated |
Dielectric Breakdown | ≥ 2000V RMS terminals to mounting surface |
Insulation Resistance | ≥ 100 MΩ |
Polarity | DC units are reverse polarity protected |
Mechanical | |
Mounting | Surface mount with one #10 (M5 x 0.8) screw |
Dimensions |
H 50.8 mm (2”) W 50.8 mm (2”) D 38.1 mm (1.51”) |
Termination | 0.25 in. (6.35 mm) male quick connect terminals |
Environmental | |
Operating/Storage Temperature | -40° to 60°C / -40° to 85°C |
Humidity | 95% relative, non-condensing |
Weight | ≅ 3.9 oz (111 g) |