Littelfuse KRD93115MA, KRD9 Series, 24VDC, One Shot Time Delay Relay SPDT (1 Form C) Fixed, 15 Min Delay 10A @ 125VAC Chassis Mount

In stock
SKU: KRD93115MA
Regular price $138.74
Rated voltage
Function type

Use this text to encourage communication or promote sharing on social networks.

You can also add links

The KRD9 Series microcontroller timing circuit provides excellent repeat accuracy and stability. Cost effective approach for OEM applications that require small size, isolation, reliability, and long life.

Operation (Retriggerable Single Shot)

Function Type A (Output Initially De-energized): Input voltage must be applied prior to and during timing. When the initiate switch is closed, (momentary or maintained) the output energizes and the time delay starts. On completion of the delay, the output de-energizes. The unit will time out if S1 remains in the open or closed position for the full time delay. Reclosing the initiate switch resets the time delay and restarts timing; the output remains energized. The output will not energize if the initiate switch is closed when input voltage is applied.

Function Type B (Output Initially Energized): Upon application of input voltage, the output energizes and the time delay starts. At the end of the time delay, the load de-energizes. The unit will time out if S1 remains in the open or closed position for the full time delay. Closing (re-closing) the initiate switch resets the time delay and restarts timing; the output remains energized.

Reset: The time delay and the output are reset when input voltage is removed.

Pre-order 6-8 Weeks

Specifications

Time Delay
Type Microcontroller based with watchdog circuitry
Range 0.1s - 1000m in 6 adjustable ranges or fixed
Repeat Accuracy ±0.5% or 20ms, whichever is greater
Tolerance (Factory Calibration) ≤ ± 5%
Reset Time ≤ 150ms
Initiate Time ≤ 40ms; ≤ 750 operations per minute
Time Delay vs Temp. & Voltage ≤ ±5%
Input
Voltage 12, 24 or 110VDC; 24, 120 or 230VAC
Tolerance 12VDC & 24VDC/AC -15% - +20%
110VDC, 120 or 230VAC -20% - +10%
AC Line Frequency/DC Ripple 50/60 Hz / ≤ 10%
Power Consumption AC ≤ 2VA; DC ≤ 2W
Output
Type Isolated relay contacts
Form SPDT
Rating (at 40°C) 10A resistive @ 125VAC;
5A resistive @ 230VAC & 28VDC;
1/4 hp @ 125VAC
Max. Switching Voltage 250VAC
Life (Operations) Mechanical - 1 x 10⁷ ; Electrical - 1 x 10⁵
Protection
Polarity DC units are reverse polarity protected
Circuitry Encapsulated
Isolation Voltage ≥ 1500V RMS input to output
Insulation Resistance ≥ 100 MΩ
Mechanical
Mounting Surface mount with one #10 (M5 x 0.8) screw
Dimensions H 50.8 mm (2”)
W 50.8 mm (2”)
D 30.7 mm (1.21”)
Termination 0.25 in. (6.35 mm) male quick connect terminals
Environmental
Operating/Storage Temperature -20° to 60°C / -40° to 85°C
Humidity 95% relative, non-condensing
Weight ≅ 2.6 oz (74 g)