The LLC8 Series is a low cost, single-probe conductive liquid level control designed for low liquid level cutoff protection. It offers a factory fixed time delay of 1 - 60s and is available for input voltages of 24, 120, or 230VAC. LED indicator illuminates whenever the LLC8’s isolated, 10A, SPDT output relay is energized. Sense resistance is fixed from 5K - 250KΩ. Available with manual/automatic reset or a special manual reset with a power outage feature that auto resets the unit when power is restored and the water level is acceptable. 24 and 120VAC units are UL recognized as limit switches under UL353 (230VAC units are UL 508) and CSA certified under Standard 14.

Operation

Automatic Reset (Reset switch not connected): When liquid rises to low level cutoff probe, output relay and LED indicator energize. When liquid falls below the low level cutoff probe, the output relay and LED indicator de-energize after a fixed time delay.

Manual Reset (Reset switch connected): When the liquid level falls below low level probe, the output relay and LED de-energize after a fixed time delay. When the liquid level rises to low level probe, the output relay and LED indicator remain de-energized until the NC manual reset switch is opened; then they energize immediately.

Power Outage Manual Reset (Reset switch connected): A power outage causes the output relay and LED indicator to de-energize. Upon restoration of power, if the liquid is touching the low level probe, the output relay and LED indicator will re-energize. If the liquid level is below the low level probe, the output relay and LED indicator remain de-energized until the NC reset switch is opened.

Specifications

Control
Type Resistance sensing for conductive liquids with time delay
Sense Voltage 12VAC nominal at probe terminals
Sense Resistance Fixed 5K - 250KΩ
Sense Resistance Tolerance ±10%
Input
Voltage 120VAC
Tolerance -20% - 10%
AC Line Frequency 50/60 Hz
Time Delay
Tolerance ±20%
Repeat Accuracy ±10%
Time Delay vs Temp. & Voltage ±10%
Power Outage Reset Delay ≤1s
Output
Type Electromechanical relay
Form solated, SPDT
Rating 10A resistive @ 120/240VAC;
1/4 hp @ 125VAC; 1/2 hp @ 250VAC
Protection
Isolation Voltage ≥ 2500V RMS input to output terminals
Mechanical
Mounting 0.5 in. (12.7 mm) x .187 (4.76 mm) dia. nylon standoffs (3)
Termination
Dimensions H  101.6 mm (4.0”)
W 63.5 mm (2.5”)
D  47.8 mm (1.88”)
Electrical 0.25 in. (6.35 mm) male quick connect terminals
Reset Switch & Probe(s) 0.187 x 0.03 in. (4.75 x 0.76 mm) male quick connect terminals
Environmental
Operating/Storage Temperature -40° to 60°C / -40° to 80°C
Coating Printed circuit board is conformal coated to resist moisture & corrosion
Humidity 95% relative, non-condensing