Littelfuse MPU-32-01-00, MPU-32 Series, Motor Protection Unit, 65-265VAC/80-275DC, TIA-232 & TIA-485, Using MPU-CIM-00-00, purchased separately
FOR ALL ORDERS OUTSIDE CANADA, CUSTOMERS ARE RESPONSIBLE FOR ANY IMPORT DUTIES, TARIFFS, TAXES, AND CUSTOMS FEES THAT MAY APPLY TO THEIR ORDERS.
Couldn't load pickup availability
Use this text to encourage communication or promote sharing on social networks.
The MPU-32 series Motor Protection Unit is used to provide current and temperature-based protection, metering, and datalogging for three-phase, low-voltage, medium-horsepower induction motors. This relay is ideal for retrofitting and upgrading obsolete or aging motor protection using existing CTs. The MPU-32 can be programmed using the front-panel operator interface, the TIA-232 port, or an optional communications network. See the PMA Family of Panel Mount Adapter Kits to replace common obsolete relays.
Motor Protection Unit
• Three ac-current inputs
• Earth-leakage-CT input
• Programmable digital input
• 24 V dc source for digital input
• Programmable 4–20-mA analog output
• Onboard temperature-sensor input
• 100-Ω-Platinum RTD or PTC
• Three programmable output relays
• Local RS-232 communications, optional network communications
• PC-interface software (SE-Comm-RIS)
• 4 line x 20 character backlit LCD display
• Keypad for programming and display selection
• 4 LEDs; 1 user programmable
Specifications
| Protective Functions (IEEE Device Numbers) | Overload (49, 51), Phase reverse (current) (46), Overcurrent (50, 51), Jam, Ground fault (50G/N, 51G/N), PTC overtemperature (49), RTD temperature (38, 49), Unbalance (current) (46), Starts per hour (66), Differential (87), Phase loss (current) (46), Undercurrent (37) |
| Input Voltage | 65-265 V ac, 25 VA; 80-275 V dc, 25 W |
| Power-Up Time | 800 ms at 120 V ac |
| Ride-Through Time | 100 ms minimum |
| 24-Vdc Source | 100 mA maximum |
| AC Measurements | True RMS and DFT, Peak, 16 samples/cycle, and positive and negative sequence of fundamental |
| Frequency | 50, 60 Hz or ASD |
| Output Contacts | Three Form C programmables |
| Communications | TIA-232 (standard); TIA-485, DeviceNet™, Ethernet (optional) |
| Analog Output | 4-20 mA, programmable |
| Conformally Coated | Standard feature |
| Warranty | 10 years |
| Control Unit Mounting | Panel (standard), Surface (with MPU-32-SMK converter kit) |
| Current Input Module Mounting | DIN, Surface |
| Certification & Compliance | |
| CSA |
CSA, Canada and USA (CSA C22.2 No. 14, CSA C22.2 No. 213-M1987 (RTD module only), CSA E60079-15:02 (RTD module only)) |
| CE | EN 60255-26, IEC 61010-1 |
| UL | UL Recognized (UL 508, UL 1053, UL 60079-15 (RTD module only)) |
| RCM | RCM |