Littelfuse MPU-32-01-01, MPU-32 Series, Motor Protection Unit, 65-265VAC/80-275DC, TIA-232 & TIA-485, Onboard inputs for 1-A phase CTs

In stock
SKU: MPU-32-01-01
Regular price $6,497.77
Rated voltage
 More payment options

Pickup available at 220 Alden Road

Usually ready in 24 hours

Use this text to encourage communication or promote sharing on social networks.

You can also add links

The MPU-32 series Motor Protection Unit is used to provide current and temperature-based protection, metering, and datalogging for three-phase, low-voltage, medium-horsepower induction motors. This relay is ideal for retrofitting and upgrading obsolete or aging motor protection using existing CTs. The MPU-32 can be programmed using the front-panel operator interface, the TIA-232 port, or an optional communications network. See the PMA Family of Panel Mount Adapter Kits to replace common obsolete relays.

 Motor Protection Unit

• Three ac-current inputs
• Earth-leakage-CT input
• Programmable digital input
• 24 V dc source for digital input
• Programmable 4–20-mA analog output
• Onboard temperature-sensor input
• 100-Ω-Platinum RTD or PTC
• Three programmable output relays
• Local RS-232 communications, optional network communications
• PC-interface software (SE-Comm-RIS)
• 4 line x 20 character backlit LCD display
• Keypad for programming and display selection
• 4 LEDs; 1 user programmable

Pre-order 6-8 Weeks

Specifications

Protective Functions (IEEE Device Numbers) Overload (49, 51), Phase reverse (current) (46), Overcurrent (50, 51), Jam, Ground fault (50G/N, 51G/N), PTC overtemperature (49), RTD temperature (38, 49), Unbalance (current) (46), Starts per hour (66), Differential (87), Phase loss (current) (46), Undercurrent (37)
Input Voltage 65-265 V ac, 25 VA; 80-275 V dc, 25 W
Power-Up Time 800 ms at 120 V ac
Ride-Through Time 100 ms minimum
24-Vdc Source 100 mA maximum
AC Measurements True RMS and DFT, Peak, 16 samples/cycle, and positive and negative sequence of fundamental
Frequency 50, 60 Hz or ASD
Output Contacts Three Form C programmables
Communications TIA-232 (standard); TIA-485, DeviceNet™, Ethernet (optional)
Analog Output 4-20 mA, programmable
Conformally Coated Standard feature
Warranty 10 years
Control Unit Mounting Panel (standard), Surface (with MPU-32-SMK converter kit)
Current Input Module Mounting DIN, Surface
Certification & Compliance
CSA CSA, Canada and USA
(CSA C22.2 No. 14, CSA C22.2 No. 213-M1987 (RTD module only), CSA E60079-15:02 (RTD module only))
CE EN 60255-26, IEC 61010-1
UL UL Recognized (UL 508, UL 1053, UL 60079-15 (RTD module only))
RCM RCM