Littelfuse PC-102CICI-DL, PC-102 Series, Dual Seal-Leak Detector, 120VAC

In stock
SKU: PC-102CICI-DL
Regular price $327.28
Rated voltage
⚠️ IMPORT NOTICE
FOR ALL ORDERS OUTSIDE CANADA, CUSTOMERS ARE RESPONSIBLE FOR ANY IMPORT DUTIES, TARIFFS, TAXES, AND CUSTOMS FEES THAT MAY APPLY TO THEIR ORDERS.

Use this text to encourage communication or promote sharing on social networks.

You can also add links

The PC-102 is a dual-channel switch that provides dual protection against seal failures and over-temperature in submersible pumping applications.

Both units have two form-C isolated output relays and two LEDs, which illuminate when each associated output relay is energized.

The sensitivity adjustment (4.7k-100kOhms) allows you to define the input impedance at which the output relays will change state. The sensitivity for the over-temperature detector can be set to 4k Ohms with use of the DIP switches.

Specifications

Input Characteristics  
Frequency 50/60 Hz
Functional Characteristics
Probe Sense Voltage 5 V dc pulsed
Sensitivity 4.7k-100kΩ
Sensitivity (for temp) Selectable 4kΩ with DIP switches
Input Logic Direct or inverted
Debounce Time Delay 0.5 or 2 seconds
Output Characteristics
Relay Output Rating (2 Form C isolated) Pilot Duty              180VA @ 120VAC, C150
General Purpose  5A @ 240VAC
General Characteristics
Temperature Range -20° to 55°C (-4° to 131°F)
Maximum Input Power 2 W
Depluggable Connector Phoenix Contact-Series MSTB plugs
Output Relay
Status Indicators LEDs
Terminal Torque 4.5 in.-lbs.
Wire 12-20 AWG
Standards Passed
Electrostatic Discharge (ESD) IEC 61000-4-2, Level 3, 6 kV contact, 8 kV air
Radio Frequency Immunity (RFI) IEC 61000-4-3, Level 3, 10V/m
Fast Transients IEC 61000-4-4, Level 3, 4kV input power
2kV inputs/outputs
Safety Marks UL        UL508 (File #E68520)
Dimensions H 88.9 mm (3.5”)
W 52.93 mm (2.08”)
D 59.69 mm (2.35”)
Weight 0.9 lb. (14.4 oz., 408.23 g)
Mounting Method 35mm DIN rail or Surface Mount