Littelfuse PGR-3100, PGR-3100 Series, Ground-Fault Indication System, 600VAC
Couldn't load pickup availability
Use this text to encourage communication or promote sharing on social networks.
The PGR-3100 indicates the presence of voltage on each phase of a three-phase system. The LEDs on the panel illuminate when voltage is present. When a ground-fault occurs, the voltage on the faulted phase reduces to ground potential, causing the LEDs for the faulted phase to dim and the LEDs for the unfaulted phases to become brighter. Ungrounded ac systems are required by the National Electrical Code (NEC®) Article 250.21(B) and the Canadian Electrical Code Part 1, Section 10-106 (2) to have ground detectors, such as the PGR-3100, installed on the system. External potential transformers (PTs) can be used to step down system voltage, allowing the PGR-3100 to be applied to any system voltage. PTs are not required for system voltages up to 600 V ac.
Specifications
Input Voltage | Up to 600 V ac 50/60 Hz |
Indicator Off Voltage | < 30 V ac line to ground |
Dimensions |
H 88.9 mm (3.5”) W 108 mm (4.3”) D 54 mm (2.1”) |
Test Button | Local |
Approvals | CSA certified, UL Listed |
Conformally Coated | Standard feature |
Warranty | 5 years |
Mounting | Panel |