Littelfuse PLM9405, PLM Series, Voltage Asymmetry, Voltage Sensing AC, Phase Loss 480VAC, SPDT (1 Form C)
Couldn't load pickup availability
Use this text to encourage communication or promote sharing on social networks.
The PLM Series is a 3-phase voltage monitor that continuously monitors each of the three phases. Monitors both delta and wye systems and no connection to neutral is required. The microcontroller circuit design protects against undervoltage, voltage unbalance, phase loss and phase reversal. Protection is assured when regenerated voltages are present.
Operation
The output relay is energized and the LED glows green when all voltages are acceptable and the phase sequence is correct. Under and unbalanced voltages must be sensed for a continuous trip delay period before the relay de-energizes. Reset is automatic upon correction of the fault condition. The output relay will not energize if a fault condition is sensed as power is applied. The LED flashes red during the trip delay, then glows red when the output de-energizes. The LED flashes green/red if phase reversal is sensed
Field Adjustment
Set voltage adjustment knob at the desired operating line voltage for the equipment. This adjustment automatically sets the undervoltage trip point. Apply power. If the PLM fails to energize, (LED glows red) check wiring of all three phases, voltage, and phase sequence. If phase sequence is incorrect, the LED flashes green/red. To correct this, swap any two line voltage connections at the mounting socket. No further adjustment should be required.
*CAUTION: Select an octal socket rated for 600VAC operation.
Line Voltage | |
Type | 3-phase delta or wye with no connection to neutra |
Operating Voltage |
Model Adj. Line Line Voltage Max Voltage Range 240 200-240VAC 270VAC 380 360-430VAC 480VAC 480 400-480VAC 530VAC |
AC Line Frequency | 50/100 Hz |
Phase Sequence | ABC |
Power Consumption |
≅ 2W for 240V units ≅ 3W for 380 - 480V units |
Low Voltage & Voltage Unbalance | |
Type | Voltage detection with delayed trip & automatic reset |
Low Voltage |
Trip 88 - 92% of adjusted line voltage Reset Voltage Plus 3% of trip voltage |
Voltage Unbalance |
Trip Factory fixed from 4 - 8% Reset on Balance -0.7% unbalance typical |
Trip Delay |
Range Factory fixed from 2 - 20s Tolerance ±15% |
Phase Reversal & Phase Loss | |
Response Time | ≤ 200ms |
Phase Loss | > 35% unbalance |
Reset | Automatic |
Output | |
Type | Electromechanical relay |
Form | Isolated, SPDT |
Rating |
10A resistive @ 240VAC, 277VAC max; 1/2 Hp @ 240VAC; 1/4 Hp @ 120VAC |
Life | Life Mechanical - 1 x 10⁷; Electrical - 1 x 10⁵ |
Protection | |
Surge | IEEE C62.41-1991 Level B |
Isolation Voltage | ≥ 2500V RMS input to output |
Mechanical | |
Mounting* | 8-pin plug-in socket rated 600VAC |
Dimensions |
H 81.3 mm (3.2”) W 60.7 mm (2.39”) D 45.2 mm (1.78”) |
Environmental | |
Operating/Storage Temperature | -40° to 60°C / -40° to 85°C |
Weight | ≅ 4.4 oz (125 g) |