Littelfuse PLM9805, PLM Series, Voltage Asymmetry, Voltage Sensing AC, Phase Loss 480VAC, SPDT (1 Form C)

In stock
SKU: PLM9805
Regular price $272.72
Rated voltage
Voltage unbalance (fixed)

Use this text to encourage communication or promote sharing on social networks.

You can also add links

The PLM Series is a 3-phase voltage monitor that continuously monitors each of the three phases. Monitors both delta and wye systems and no connection to neutral is required. The microcontroller circuit design protects against undervoltage, voltage unbalance, phase loss and phase reversal. Protection is assured when regenerated voltages are present.

Operation
The output relay is energized and the LED glows green when all voltages are acceptable and the phase sequence is correct. Under and unbalanced voltages must be sensed for a continuous trip delay period before the relay de-energizes. Reset is automatic upon correction of the fault condition. The output relay will not energize if a fault condition is sensed as power is applied. The LED flashes red during the trip delay, then glows red when the output de-energizes. The LED flashes green/red if phase reversal is sensed

Field Adjustment
Set voltage adjustment knob at the desired operating line voltage for the equipment. This adjustment automatically sets the undervoltage trip point. Apply power. If the PLM fails to energize, (LED glows red) check wiring of all three phases, voltage, and phase sequence. If phase sequence is incorrect, the LED flashes green/red. To correct this, swap any two line voltage connections at the mounting socket. No further adjustment should be required.

Pre-order 6-8 Weeks

*CAUTION: Select an octal socket rated for 600VAC operation.

Line Voltage  
Type        3-phase delta or wye with no connection to neutra
Operating Voltage Model             Adj. Line Line       Voltage Max
                      Voltage Range
240                200-240VAC             270VAC
380                360-430VAC             480VAC
480                400-480VAC             530VAC
AC Line Frequency 50/100 Hz
Phase Sequence ABC
Power Consumption ≅ 2W for 240V units
≅ 3W for 380 - 480V units
Low Voltage & Voltage Unbalance
Type Voltage detection with delayed trip & automatic reset
Low Voltage Trip         88 - 92% of adjusted line voltage
Reset      Voltage Plus 3% of trip voltage
Voltage Unbalance Trip                           Factory fixed from 4 - 8%
Reset on Balance     -0.7% unbalance typical
Trip Delay Range         Factory fixed from 2 - 20s
Tolerance    ±15%
Phase Reversal & Phase Loss
Response Time ≤ 200ms
Phase Loss > 35% unbalance
Reset Automatic
Output
Type Electromechanical relay
Form Isolated, SPDT
Rating 10A resistive @ 240VAC, 277VAC max;
1/2 Hp @ 240VAC; 1/4 Hp @ 120VAC
Life Life Mechanical - 1 x 10⁷; Electrical - 1 x 10⁵
Protection
Surge IEEE C62.41-1991 Level B
Isolation Voltage ≥ 2500V RMS input to output
Mechanical
Mounting* 8-pin plug-in socket rated 600VAC
Dimensions H 81.3 mm (3.2”)
W 60.7 mm (2.39”)
D 45.2 mm (1.78”)
Environmental
Operating/Storage Temperature -40° to 60°C / -40° to 85°C
Weight ≅ 4.4 oz (125 g)