Littelfuse SB5060-011-0, SB5000 Series, Industrial Shock Block for Personnel Protection, 60A, 208VAC, UL 943 / UL 1053 EGFPD

In stock
SKU: SB5060-011-0
Regular price $4,639.17
Rated voltage
Ampere rating

Use this text to encourage communication or promote sharing on social networks.

You can also add links

 

Equipment Ground-Fault Protective Device (EGFPD)

Industrial Shock Block is also available with adjustable protection settings as an EGFPD. The EGFPD models can be set to trip at 6 mA or from 10–100 mA in increments of 10 mA. This offers more flexibility since GFCI devices are not allowed to have an adjustable trip level.

Ratings and Models

Industrial Shock Block (GFCI & EGFPD) is available for three-phase voltages from 208 to 600 V with a maximum full load current up to 100 A. The power system can be either solidly or high-resistance grounded, and the load must be three-phase without a neutral. The standard enclosure is IP 69K/NEMA 4X and outdoor rated, suitable for all industrial environments including high temperature washdown used in food production.

Ground Wire (Load-Ground) Monitor

The Industrial Shock Block also monitors the ground wire (load-ground) connection between the Industrial Shock Block and load. This is a required feature for Class C and D GFCI devices and is recommended for Class A GFCI and EGFPD devices. If the ground-return path is broken, the Industrial Shock Block will trip and provide an alarm by changing the state of the alarm contacts. This monitoring circuit includes an extra wire (pilot wire) between the Industrial Shock Block and load. At the load, the pilot wire is connected to a termination device. The other end of the termination device is connected to the load ground (typically the enclosure).

Specifications

Voltage Rating 208 V
Current Rating  60 A
System Type Three-phase, 3-wire (no neutral), 60 Hz; Single-phase, 2-wire (no neutral), 60 Hz;
Single-phase, 3-wire (with neutral), 60 Hz for EGFPD versions only
Short-Circuit Current Rating 10,000 A (for SB5032 and SB5060)
Trip Level Settings Fixed at 6 mA (Class A models); Fixed at 20 mA (Class C/D models)
Selectable 6, 10, 20, 30, 40, 50, 60, 70, 80, 90, 100 mA (EGFPD models)
Trip Time Setting Inverse time curve according to UL 943
Ground Monitoring Circuit Selectable short or Zener termination; Fail-safe; CSA M421 compliant
Enclosure IP 69K and NEMA 4X (Outdoor), Polycarbonate, Lockable
Operating Temperature -35 °C (-31 °F) to 40 °C (104 °F), up to 66 °C (151 °F) with derating
Dimensions H 285.6 mm (11.25 in.); W 244.4 mm (9.62 in.);    D 119.6 mm (4.71 in.) – for 32 A and 60 A
Certification & Compliance
UL Listed (all models) UL1998
CSA (SB5032, SB5060 models) LR 53428
cULus Listed Class A GFCI (UL 943) E330856
EGFPD (UL 943/UL 1053) E359574
UL Listed Class C, D SPGFCI (UL 943C) E352763