Littelfuse SB6100-111-0, SB6000 Series, Industrial Shock Block for Personnel Protection, 240VAC, UL 943/UL 1053 Equipment ground-fault protective device (EGFPD), Enclosed Model, NEMA 4X

In stock
SKU: SB6100-111-0
Regular price $12,240.75
Rated voltage

Use this text to encourage communication or promote sharing on social networks.

You can also add links

 

Equipment Ground-Fault Protective Device (EGFPD)

Industrial Shock Block is also available with adjustable protection settings as an EGFPD. The EGFPD models can be set to trip at 6 mA or from 10-100 mA in increments of 10 mA. This offers more flexibility since GFCI devices are not allowed to have an adjustable trip level.

Rating and Models

Industrial Shock Block (GFCI & EGFPD) is available for three-phase voltages from 208 to 600 V with a maximum full load current of 100 A, and a built-in overcurrent protection supplied by Littelfuse Class T fuses. The power system can be either solidly or high-resistance grounded and the load must be three phase without a neutral.

Two options for enclosures are available: UL-recognized open-chassis models are available for installation in existing electrical enclosures and UL-listed enclosed models include a NEMA-4X enclosure for stand-alone installations.

Ground Wire (Load-Ground) Monitor

The Industrial Shock Block also monitors the ground wire (load-ground) connection between the Industrial Shock Block and load. This is a required feature for Class C and D GFCI devices and and is recommended for Class A GFCI and EGFPD devices. If the connection is broken, the Industrial Shock Block will trip and provide an alarm by changing the state of the alarm contacts. This monitoring circuit includes an extra wire (pilot wire) between the Industrial Shock Block and load (since the monitoring current is low, only a small wire is required). At the load, the pilot wire is connected to a termination device. The other end of the termination device is connected to the load ground (typically the enclosure).

Pre-order 6-8 Weeks

Voltage Rating 240 V
Current Rating 100 A (continuous)
System Type 3-phase, 3-wire (no neutral), 60 Hz
Short-Circuit Current Rating 50,000 A
Trip Level Settings Selectable (6, 10, 20, 30, 40, 50, 60, 70, 80, 90, 100 mA), fixed at 6 mA, or fixed at 20 mA
Trip Time Setting Inverse time trip curve
Enclosure NEMA 4X, Polyester, Lockable
Operating Temperature –35 °C (–31 °F) to + 40 °C(104 °F), up to + 66 °C (151 °F) with derating
Dimensions Enclosed: H 453.8 mm (17.9”);
W 406.2 mm (16.0”); D 223.3 mm (8.8”)
Open-chassis: H 455.0 mm (17.9”);
W 340.7 mm (13.4”); D 174.9 mm (6.8”)
Wiring Requirements 2/0 AWG (maximum)
Approval GFCI: UL Listed (enclosed models) and UL Recognized Component (open-chassis models)
EGFPD: cULus Listed (enclosed models) and cURus Recognized Component (open-chassis models);
UL1998 Compliant (revision 01 or higher);
All models except SB6100-02x-0 CSA Certified
Warranty 1 year