Littelfuse SE-325 Series, Neutral-Grounding-Resistor Monitor, 120VAC

In stock
SKU: SE-325
Regular price $1,949.48
Rated voltage

Use this text to encourage communication or promote sharing on social networks.

You can also add links

The SE-325 Neutral-Grounding-Resistor Monitor is used on resistance-grounded systems up to 25 kV to monitor the integrity of the neutral-to-ground path and to detect ground faults. It measures current and voltage in a transformer or generator neutral-to-ground connection and continuity of the neutral-grounding resistor (NGR). The SE-325 coordinates these three measurements to detect a loose connection, corrosion, ground fault, or NGR failure, and provides one alarm or trip output contact.

IEEE Device Numbers Ground Fault (50G/N, 51G/N),
Overvoltage (59N), Lockout Relay (86),
Checking Relay (3) 
Input Voltage See ordering information
Dimensions H 150 mm (5.9");
W 109 mm (4.3");
D 100 mm (4.0")
GF Trip Level Settings 0.5-4.0 A
GF Trip Time Settings 0.1-2.0 s
RF Trip-Level Settings 20-400 Vac (≤5 kV systems)
100-2,000 Vac (>5 kV systems)
Contact Operating Mode Selectable fail-safe or non-fail-safe
Reset Button Standard feature
Output Contacts Form A
Approvals CSA certified, UL Listed (E340889),
C-Tick (Australian)
Conformally coated Standard feature
Warranty 5 years
Mounting Surface