Littelfuse SE-330AU-00-01, SE-330AU Series, Neutral-Earthing-Resistor Monitor, 120/240VAC/DC, Communications USB, Normally Closed
Couldn't load pickup availability
Use this text to encourage communication or promote sharing on social networks.
The SE-330AU is an advanced earth-fault and earthing-resistor monitoring relay for low- and medium-voltage transformers and generators. It monitors neutral current, neutral-to-earth voltage, and neutral-to-earth resistance. It provides continuous monitoring of the neutral-to-earth path to verify that the neutralearthing resistor (NER) is intact. This is of utmost importance— an open NER renders current-sensing earth-fault protection inoperative and could result in a false belief that the system is functioning properly. The SE-330AU earth-fault function complies with AS/NZS 2081.3:2002. Outputs include four relay outputs, and an analog output. A mini USB port is included to view measured values, configure settings, and check event records. An on-board micro SD card can be used for long-term data logging. Network communications options are available. For non-AS/NZS 2081 applications, see the SE-330 or SE-330HV.
Resistor Monitoring
The SE-330AU combines the measured values of resistance, current, and voltage to continuously determine that the NER is intact. It is able to detect a resistor failure with or without an earth fault present. Sensing resistors are matched to the system voltage and are used to monitor NGRs on systems up to 35 kV.
Earth-Fault Monitoring
The SE-330AU uses a 5- or 30-A-primary current transformer to provide a pickup-setting range of 0.125 to 5 A or 0.75 to 30 A to comply with AS/NZS 2081.3:2002. DFT filtering ensures that false trips due to harmonic noise from adjustable-speed drives do not occur. Open-CT detection is provided.
Pre-order 6-8 Weeks
Specifications
Input Voltage | 120/240VAC/DC |
Dimensions |
H 213 mm (8.4”), W 98 mm (3.9”), D 132 mm (5.2”) |
GF Trip Level Settings | 0.125 to 30 A |
GF Trip Time Settings | 0.1 to 0.5 s |
Vn Trip-Level Settings |
20-2,000 Vac (≤5 kV systems) 100-10,000 Vac (>5 kV systems |
Output Contacts | Two Form A, Two Form C |
Operating Mode | Fail-Safe |
Harmonic Filtering | Standard feature |
Reset | Front panel push button and remote input |
Approvals | C-Tick (Australian), CE |
Communications |
Mini USB (standard); DeviceNet (optional), IEC 61850(optional), Modbus TCP and EtherNet/IP (optional) |
Analog Output | 4-20 mA, self or loop powered |
Conformally coated | Standard feature |
Warranty | 5 years |
Mounting | Panel and Surface (optional) |