Littelfuse SE-330AU-01-00, SE-330AU Series, Neutral-Earthing-Resistor Monitor, 120/240 VAC/DC, Communications USB DeviceNet, Normally Open

In stock
SKU: SE-330AU-01-00
Regular price $8,499.01
Rated voltage
 More payment options

Pickup available at 220 Alden Road

Usually ready in 24 hours

Use this text to encourage communication or promote sharing on social networks.

You can also add links


The SE-330AU is an advanced earth-fault and earthing-resistor monitoring relay for low- and medium-voltage transformers and generators. It monitors neutral current, neutral-to-earth voltage, and neutral-to-earth resistance. It provides continuous monitoring of the neutral-to-earth path to verify that the neutralearthing resistor (NER) is intact. This is of utmost importance— an open NER renders current-sensing earth-fault protection inoperative and could result in a false belief that the system is functioning properly. The SE-330AU earth-fault function complies with AS/NZS 2081.3:2002. Outputs include four relay outputs, and an analog output. A mini USB port is included to view measured values, configure settings, and check event records. An on-board micro SD card can be used for long-term data logging. Network communications options are available. For non-AS/NZS 2081 applications, see the SE-330 or SE-330HV.
Resistor Monitoring
The SE-330AU combines the measured values of resistance, current, and voltage to continuously determine that the NER is intact. It is able to detect a resistor failure with or without an earth fault present. Sensing resistors are matched to the system voltage and are used to monitor NGRs on systems up to 35 kV.
Earth-Fault Monitoring
The SE-330AU uses a 5- or 30-A-primary current transformer to provide a pickup-setting range of 0.125 to 5 A or 0.75 to 30 A to comply with AS/NZS 2081.3:2002. DFT filtering ensures that false trips due to harmonic noise from adjustable-speed drives do not occur. Open-CT detection is provided.

Pre-order 6-8 Weeks

Specifications

Input Voltage 120/240VAC/DC
Dimensions H 213 mm (8.4”),
W 98 mm (3.9”),
D 132 mm (5.2”)
GF Trip Level Settings 0.125 to 30 A
GF Trip Time Settings 0.1 to 0.5 s
Vn Trip-Level Settings 20-2,000 Vac (≤5 kV systems)
100-10,000 Vac (>5 kV systems
Output Contacts Two Form A, Two Form C
Operating Mode Fail-Safe
Harmonic Filtering Standard feature
Reset Front panel push button and remote input
Approvals C-Tick (Australian), CE
Communications Mini USB (standard);
DeviceNet (optional),
IEC 61850(optional),
Modbus TCP and EtherNet/IP (optional)
Analog Output 4-20 mA, self or loop powered
Conformally coated Standard feature
Warranty 5 years
Mounting Panel and Surface (optional)