Littelfuse SE-330AU-03-01, SE-330AU Series, Neutral-Earthing-Resistor Monitor, 120/240 VAC/DC, Communications USB Ethernet (Dual RJ45), Normally Closed
Pickup available at 220 Alden Road
Usually ready in 24 hours
Use this text to encourage communication or promote sharing on social networks.
The SE-330AU is an advanced earth-fault and earthing-resistor monitoring relay for low- and medium-voltage transformers and generators. It monitors neutral current, neutral-to-earth voltage, and neutral-to-earth resistance. It provides continuous monitoring of the neutral-to-earth path to verify that the neutralearthing resistor (NER) is intact. This is of utmost importance— an open NER renders current-sensing earth-fault protection inoperative and could result in a false belief that the system is functioning properly. The SE-330AU earth-fault function complies with AS/NZS 2081.3:2002. Outputs include four relay outputs, and an analog output. A mini USB port is included to view measured values, configure settings, and check event records. An on-board micro SD card can be used for long-term data logging. Network communications options are available. For non-AS/NZS 2081 applications, see the SE-330 or SE-330HV.
Resistor Monitoring
The SE-330AU combines the measured values of resistance, current, and voltage to continuously determine that the NER is intact. It is able to detect a resistor failure with or without an earth fault present. Sensing resistors are matched to the system voltage and are used to monitor NGRs on systems up to 35 kV.
Earth-Fault Monitoring
The SE-330AU uses a 5- or 30-A-primary current transformer to provide a pickup-setting range of 0.125 to 5 A or 0.75 to 30 A to comply with AS/NZS 2081.3:2002. DFT filtering ensures that false trips due to harmonic noise from adjustable-speed drives do not occur. Open-CT detection is provided.
Pre-order 6-8 Weeks
Specifications
Input Voltage | 120/240VAC/DC |
Dimensions |
H 213 mm (8.4”), W 98 mm (3.9”), D 132 mm (5.2”) |
GF Trip Level Settings | 0.125 to 30 A |
GF Trip Time Settings | 0.1 to 0.5 s |
Vn Trip-Level Settings |
20-2,000 Vac (≤5 kV systems) 100-10,000 Vac (>5 kV systems |
Output Contacts | Two Form A, Two Form C |
Operating Mode | Fail-Safe |
Harmonic Filtering | Standard feature |
Reset | Front panel push button and remote input |
Approvals | C-Tick (Australian), CE |
Communications |
Mini USB (standard); DeviceNet (optional), IEC 61850(optional), Modbus TCP and EtherNet/IP (optional) |
Analog Output | 4-20 mA, self or loop powered |
Conformally coated | Standard feature |
Warranty | 5 years |
Mounting | Panel and Surface (optional) |