Littelfuse SE-330AU-21-01, SE-330AU Series, Neutral-Earthing-Resistor Monitor, 48VDC, Communications USB DeviceNet, Normally Closed

In stock
SKU: SE-330AU-21-01
Regular price $8,423.95
Rated voltage

Use this text to encourage communication or promote sharing on social networks.

You can also add links


The SE-330AU is an advanced earth-fault and earthing-resistor monitoring relay for low- and medium-voltage transformers and generators. It monitors neutral current, neutral-to-earth voltage, and neutral-to-earth resistance. It provides continuous monitoring of the neutral-to-earth path to verify that the neutralearthing resistor (NER) is intact. This is of utmost importance— an open NER renders current-sensing earth-fault protection inoperative and could result in a false belief that the system is functioning properly. The SE-330AU earth-fault function complies with AS/NZS 2081.3:2002. Outputs include four relay outputs, and an analog output. A mini USB port is included to view measured values, configure settings, and check event records. An on-board micro SD card can be used for long-term data logging. Network communications options are available. For non-AS/NZS 2081 applications, see the SE-330 or SE-330HV.
Resistor Monitoring
The SE-330AU combines the measured values of resistance, current, and voltage to continuously determine that the NER is intact. It is able to detect a resistor failure with or without an earth fault present. Sensing resistors are matched to the system voltage and are used to monitor NGRs on systems up to 35 kV.
Earth-Fault Monitoring
The SE-330AU uses a 5- or 30-A-primary current transformer to provide a pickup-setting range of 0.125 to 5 A or 0.75 to 30 A to comply with AS/NZS 2081.3:2002. DFT filtering ensures that false trips due to harmonic noise from adjustable-speed drives do not occur. Open-CT detection is provided.

Pre-order 6-8 Weeks

Specifications

Input Voltage 48VDC
Dimensions H 213 mm (8.4”),
W 98 mm (3.9”),
D 132 mm (5.2”)
GF Trip Level Settings 0.125 to 30 A
GF Trip Time Settings 0.1 to 0.5 s
Vn Trip-Level Settings 20-2,000 Vac (≤5 kV systems)
100-10,000 Vac (>5 kV systems
Output Contacts Two Form A, Two Form C
Operating Mode Fail-Safe
Harmonic Filtering Standard feature
Reset Front panel push button and remote input
Approvals C-Tick (Australian), CE
Communications Mini USB (standard);
DeviceNet (optional),
IEC 61850(optional),
Modbus TCP and EtherNet/IP (optional)
Analog Output 4-20 mA, self or loop powered
Conformally coated Standard feature
Warranty 5 years
Mounting Panel and Surface (optional)