Littelfuse T2D120A15M, T2D Series, 120VAC, On-Delay Time Delay Relay SPST-NO (1 Form A) Fixed, 5 Min Delay Chassis Mount
Couldn't load pickup availability
Use this text to encourage communication or promote sharing on social networks.
The T2D Series provides protection against short cycling of compressors and other motors. At the end of each operation, a lockout delay prevents restarting the compressor or motor until the delay is completed.
Operation (Lockout with Random Start)
Connection #1: Upon application of input voltage, a random start time delay begins. At the end of this time delay, the output is energized.
Lockout Delay: Input voltage must be applied prior to and during timing. When the thermostat or initiate switch opens, the output de-energizes and the lockout time delay begins. At the end of the lockout delay, the output is energized allowing the load to immediately energize when the initiate switch or thermostat closes.
Connection #2: Upon application of input voltage and closure of initiate switch, the time delay begins. At the end of the time delay, the output is energized and remains energized until power is removed.
Reset: Removing power resets the output and the time delay
Input | |
Voltage | 120 VAC |
Tolerance | ±20% |
AC Line Frequency | 50/60 Hz |
Output | |
Minimum Load Current | 40mA |
Rating | 1A steady state, 10A inrush at 60°C |
Voltage Drop | ≅ 2.5V @ 1A |
Time Delay | |
Initiate Time | After timing - 16ms |
Type | Analog circuitry |
Lockout & Random Start Delays |
5m fixed Note: The lockout & random start delays are the same lengt |
Tolerance | +/-30% |
Repeat Accuracy | ±1% or 20ms, whichever is greater |
Reset Time |
After timing - ≤ 16ms; During timing - ≤ 200ms |
Protection | |
Dielectric Breakdown | ≥ 2000V RMS terminals to mounting surface |
Insulation Resistance | ≥ 100 MΩ |
Mechanical | |
Mounting | Surface mount with one #10 (M5 x 0.8) screw |
Dimensions |
H 50.8 mm (2”); W 50.8 mm (2”); D 30.7 mm (1.21”) |
Termination | 0.25 in. (6.35 mm) male quick connect terminals |
Environmental | |
Operating/Storage Temperature | -20° to 60°C / -40° to 85°C |
Humidity | 95% relative, non-condensing |
Weight | ≅ 2.4 oz (68 g) |
Cooling Anticipator (24VAC Units Only) | |
Minimum Cooling Anticipator | ≥ 3,000 Ω |