The T2D Series provides protection against short cycling of compressors and other motors. At the end of each operation, a lockout delay prevents restarting the compressor or motor until the delay is completed.

Operation (Lockout with Random Start)
Connection #1: Upon application of input voltage, a random start time delay begins. At the end of this time delay, the output is energized.
Lockout Delay: Input voltage must be applied prior to and during timing. When the thermostat or initiate switch opens, the output de-energizes and the lockout time delay begins. At the end of the lockout delay, the output is energized allowing the load to immediately energize when the initiate switch or thermostat closes.
Connection #2: Upon application of input voltage and closure of initiate switch, the time delay begins. At the end of the time delay, the output is energized and remains energized until power is removed.
Reset: Removing power resets the output and the time delay

Input
Voltage 120 VAC
Tolerance ±20%
AC Line Frequency 50/60 Hz
Output
Minimum Load Current 40mA
Rating 1A steady state, 10A inrush at 60°C
Voltage Drop ≅ 2.5V @ 1A
Time Delay
Initiate Time After timing - 16ms
Type Analog circuitry
Lockout & Random Start Delays 5m fixed
Note: The lockout & random start delays are the same lengt
Tolerance +/-30%
Repeat Accuracy ±1% or 20ms, whichever is greater
Reset Time After timing - ≤ 16ms;
During timing - ≤ 200ms
Protection
Dielectric Breakdown ≥ 2000V RMS terminals to mounting surface
Insulation Resistance ≥ 100 MΩ
Mechanical
Mounting Surface mount with one #10 (M5 x 0.8) screw
Dimensions H 50.8 mm (2”); W 50.8 mm (2”);
D 30.7 mm (1.21”)
Termination 0.25 in. (6.35 mm) male quick connect terminals
Environmental
Operating/Storage Temperature -20° to 60°C / -40° to 85°C
Humidity 95% relative, non-condensing
Weight ≅ 2.4 oz (68 g)
Cooling Anticipator (24VAC Units Only)
Minimum Cooling Anticipator ≥ 3,000 Ω