Noark Ex9C0922S7, Ex9C Series, Standard IEC Contactor, Non-Reversing, 3-Pole, 9A, AC Coil, 2NO+2NC Auxiliary Contact, 500V Control Voltage, 50/60 Hz, 3NO Main Power Contact
Regular price
$35.52
Couldn't load pickup availability
Use this text to encourage communication or promote sharing on social networks.
Contactor Type
|
Ex9C Standard
|
Function
|
Full Voltage Non-Reversing (FVNR)
|
Coil Type
|
AC
|
Number of Poles
|
3
|
Rated Current
|
9 A
|
Auxiliary Contacts
|
2NO+2NC (2 Normally Open + 2 Normally Closed)
|
Control Voltage
|
500V
|
Frequency
|
50/60 Hz
|
Main Power Contacts
|
3NO
|
Response Time
|
(Operating / Closing Time) 14-30ms / 0.014-0.03 s
(Drop-Off / Opening Time) 6-20ms / 0.006-0.02 s |
Rated Operating Voltage (Ue)
|
(Aux. Contacts) 690 V
|
Rated Active Power (kW)
|
4kW (380/400Vac; AC-3)
2.2kW (230Vac; AC-3) 5.5kW (660/690Vac; AC-3) |
Rated Power (HP)
|
5HP (440-480Vac; 3-phase; UL)
1.5HP / 1-1/2HP (220-240Vac; single-phase; UL) 0.5HP / 1/2HP (110-120Vac; single-phase; UL) 3HP (200-208Vac; 3-phase; UL) 3HP (220-240Vac; 3-phase; UL) 7.5HP / 7-1/2HP (550-600Vac; 3-phase; UL) |
Degree of Protection
|
IP20 (Front Side)
|
Mounting | DIN rail Mounting (NS35/7.5) Screw Mounting On a Plate (4mm Holes) |
Dimension LxWxH in (mm) | 3.58x1.77x3.70 (91x45x94) |
Ambient Air Temperature for Operation
|
-4°F...+140°F / -20°C...+60 °C
|
Application Type
|
Direct On Line (DOL)
FVNR (Full-Voltage Non-Rv.) 6562ft / 2000m max. height above sea level |
Certifications
|
UL 508 Listed, File Number E353866, UL 60947-1 and 60947-4-1
Certified for Canada CSA standards 22.2 No. 14 under cUL testing IEC/EN 60947-4-1 CE Approved CCC Certified |