Noark Ex9SN25B6.3A, Ex9SN Series, Manual Motor Starter, Frame Ampere 25A, OFF/ON Push Button, Rated Current Range 4-6.3A
Couldn't load pickup availability
Use this text to encourage communication or promote sharing on social networks.
Manual motor starters are electromechanical protection devices for the main circuit. They are used mainly to switch motors manually ON/OFF and protect them fuse less against short circuit and loss-phase. None-fuss protection with a manual motor starter saves costs, space and ensures a quick reaction under short-circuit condition, by switching off the motor within milliseconds. Manual motor starter combinations are setup together with contactors and overload relays.
• Available with enclosed coils for protection against particle contamination
• Short-circuit protection
• Disconnect function
• Overload protection
• Loss-phase protection
• Suitable for three and single-phase application
• Trip-free mechanism
• Clear switch position indication ON/OFF/TRIP
Frame Size
|
25A
|
Type
|
Pushbutton
|
Rated Current Range
|
4-6.3A
|
Tripping Class
|
Class 10 A
|
Rated Insulation Voltage Ui (V)
|
IEC 690, UL/CSA 600
|
Rated operational voltage Ue (AC)
|
230/240, 400/415, 460/480, 575/600
|
Rated Impulse Withstand Voltage Uimp (V)
|
6,000
|
Rated Operational Frequency
|
50/60Hz
|
Altitude ft (m)
|
Not to exceed 6,562 (2,000)
|
Pollution Grade
|
Class III
|
Release Grade
|
10 A (SN25)
|
Degree of Protection
|
IP 20
|
Environmental Temperature
|
Working at: -4 to 131 °F (-20 to +55 °C)
|
Mounting Conditions
|
The inclination between the mounting plane and the vertical plane shall not exceed 5°.
The product shall be installed and operated at a place without obvious shake, impact and vibration. |
Certifications
|
UL 508 Listed, File Number E467185, UL 60947-1 and 60947-4-1
Certified for Canada according to CSA standards 22.2 No. 14 IEC/EN 60947-2 and 60947-4-1 CE Approved RoHS Compliant |